Time history analysis for investigation of dynamic behavioral characteristics of uninterruptible power supply system

Time history analysis for investigation of dynamic behavioral characteristics of uninterruptible... This paper presents a seismic investigation of an uninterruptible power supply system (UPS) through triaxial shake table tests. A 100-kVA uninterruptible power supply system compliant with IEC-60950 was selected as the test specimen. The input acceleration time histories were generated based on the ICC-ES AC156 code, with scaling factors ranging from 25% to 600%. Based on the test results, the damage of the UPS and dynamic characteristics of this device were evaluated and explained in terms of fundamental frequency, damping ratio, acceleration time history response, dynamic amplification factor, and relative displacement. In addition, a simplified analytical model was proposed, and a parametric study was conducted to understand the dynamic characteristics of the UPS. http://www.deepdyve.com/assets/images/DeepDyve-Logo-lg.png Journal of Structural Integrity and Maintenance Taylor & Francis

Time history analysis for investigation of dynamic behavioral characteristics of uninterruptible power supply system

Time history analysis for investigation of dynamic behavioral characteristics of uninterruptible power supply system

Journal of Structural Integrity and Maintenance , Volume 7 (2): 19 – Apr 3, 2022

Abstract

This paper presents a seismic investigation of an uninterruptible power supply system (UPS) through triaxial shake table tests. A 100-kVA uninterruptible power supply system compliant with IEC-60950 was selected as the test specimen. The input acceleration time histories were generated based on the ICC-ES AC156 code, with scaling factors ranging from 25% to 600%. Based on the test results, the damage of the UPS and dynamic characteristics of this device were evaluated and explained in terms of fundamental frequency, damping ratio, acceleration time history response, dynamic amplification factor, and relative displacement. In addition, a simplified analytical model was proposed, and a parametric study was conducted to understand the dynamic characteristics of the UPS.

Loading next page...
 
/lp/taylor-francis/time-history-analysis-for-investigation-of-dynamic-behavioral-3Wfp7rlBkw

References (24)

Publisher
Taylor & Francis
Copyright
© 2022 Korea Institute for Structural Maintenance and Inspection
ISSN
2470-5322
eISSN
2470-5314
DOI
10.1080/24705314.2021.2018792
Publisher site
See Article on Publisher Site

Abstract

This paper presents a seismic investigation of an uninterruptible power supply system (UPS) through triaxial shake table tests. A 100-kVA uninterruptible power supply system compliant with IEC-60950 was selected as the test specimen. The input acceleration time histories were generated based on the ICC-ES AC156 code, with scaling factors ranging from 25% to 600%. Based on the test results, the damage of the UPS and dynamic characteristics of this device were evaluated and explained in terms of fundamental frequency, damping ratio, acceleration time history response, dynamic amplification factor, and relative displacement. In addition, a simplified analytical model was proposed, and a parametric study was conducted to understand the dynamic characteristics of the UPS.

Journal

Journal of Structural Integrity and MaintenanceTaylor & Francis

Published: Apr 3, 2022

Keywords: Uninterruptible power supply system; shake table test; analytical model; non-structural elements; dynamic characteristics; natural frequency