Experimental Analysis of a Heat Cost Allocation Method for Apartment Buildings

Experimental Analysis of a Heat Cost Allocation Method for Apartment Buildings buildings Article Experimental Analysis of a Heat Cost Allocation Method for Apartment Buildings 1 , 2 , 2 1 1 , 2 Fabio Saba *, Vito Fernicola , Marco Carlo Masoero and Salvatore Abramo Dipartimento Energia, Politecnico di Torino, Corso Duca degli Abruzzi 24, 10129 Torino, Italy; marco.masoero@polito.it (M.C.M.); s220898@studenti.polito.it (S.A.) INRIM, Istituto Nazionale di Ricerca Metrologica, Strada delle Cacce 91, 10135 Torino, Italy; v.fernicola@inrim.it * Correspondence: fabio.saba@polito.it or f.saba@inrim.it; Tel.: +39-011-3919-927 Academic Editor: Cinzia Buratti Received: 23 January 2017; Accepted: 2 March 2017; Published: 6 March 2017 Abstract: The correct estimate of individual thermal energy consumptions, and consequently, a fair heat cost allocation among the residents of apartment buildings with centralized heating systems, represents an important driving force towards energy saving, energy efficiency and the reduction of pollutant emissions. Nowadays, in those contexts where direct heat meters cannot be used because of the layout of the hot water distribution system, electronic Heat Cost Allocators (HCAs) have the highest market share for the assessment of individual thermal energy consumptions. The uncertainty associated with the parameterization of heat cost allocation devices and the installation effects arising in real applications can negatively affect the accuracy of these devices, as far as the estimation of the individual fractions of thermal energy consumption is concerned. This work deals with the experimental analysis of a novel heat cost allocation method for apartment buildings and its comparison with conventional HCAs. The method allows the indirect estimation of the thermal energy exchanged by water radiators without the need for surface temperature measurements, reducing some of the drawbacks associated with the on-site installation. The experimental analysis was carried out in a full-scale central heating system test facility available at the Italian National Metrology Institute (INRIM) and characterized by SI-traceable direct heat meters installed on each water radiator. Keywords: heat accounting; heat cost allocators; individual heat consumption; centralized heating systems; building energy efficiency 1. Introduction Nowadays, buildings are responsible for about 40% of primary energy consumption and 36% of CO emissions in the EU. As about 35% of the EU building stock is over 50 years old, the improvement of the energy efficiency of buildings could lead to a significant reduction of the total EU energy consumption and CO emissions [1]. Space heating in apartment buildings is usually provided by outdated central heating systems, characterized by vertical hydraulic distributions with water radiators connected to the main risers. The refurbishment or the improvement of these types of heating system represents one of the main tasks towards the reduction of CO emissions and can be pursued both by replacing older thermal-hydraulic components and devices and by optimizing their operation and control. The heat cost allocation in apartment buildings, based on the assessment of the actual individual thermal energy consumptions, represents a forceful driver for the residents in order to optimize their household heating management, saving energy and money. Buildings 2017, 7, 20; doi:10.3390/buildings7010020 www.mdpi.com/journal/buildings Buildings 2017, 7, 20 2 of 19 In central heating systems characterized by vertical hydraulic distributions with water radiators of different apartments connected to the same feeding riser, direct heat metering is not feasible for the measurement of individual thermal energy consumptions. Therefore, the indirect estimation of radiator thermal power represents the basis for heat cost allocation, as well as for the design of the heating plant. The European Standard EN 442 [2,3] identifies the measurement model, defines the requirements of the measurement system and describes the procedure to characterize the thermal power exchanged by water radiators. The characteristic coefficients of the radiators, obtained by regression analysis of the experimental data as measured in a thermal chamber [4,5] compliant with the European Standard EN 442, enables an indirect estimate of the steady-state thermal power transferred from the radiator surface to the surrounding environment, once the water mean temperature and the air temperature in proximity of the heating surface are known. In apartment buildings, characterized by a central heating system with vertical feeding risers, the most widespread method for cost allocation of heating consumption makes use of electronic Heat Cost Allocators (HCAs). These devices indirectly estimate the heat consumption of each water radiator by implementing the radiator characteristic coefficients determined according to the EN 442 and by measuring the temperature difference between a specified point on the radiator surface and the surrounding indoor environment. The requirements and the test methods for these kinds of heat cost allocation devices are specified by the European Standard EN 834 [6]. Other heat cost allocation methods, based on the availability of radiator characteristic coefficients, rely on the use of suitable radiator valves for the measurement of the insertion time of each heating body, e.g., according to the Italian standard UNI/TR 11388 [7]. Nowadays, the use of direct or indirect thermal energy measurement devices for the evaluation of individual heating consumptions in apartment buildings, as well as of other sub-metering systems for water, gas and electricity consumptions, is becoming more and more related to the framework of Building Energy Management Systems (BEMS) and the Internet of Things (IoT). Several systems for automatic remote meter readings, centralization and processing of individual heat and water consumptions are commercially available on the market and allow real-time monitoring and management of energy flows. Integrated smart sensor networks provide the necessary measurement data to efficiently manage building energy systems by means of optimization algorithms. Along this line, K2n Ltd., in cooperation with Cardiff University, has produced a powerful cloud-based energy reporting and optimization system, characterized by a different approach to existing meter-based energy monitoring systems, that has been exploited in the framework of the iSERVcmb project to provide the configuration, analysis and optimization of about 2800 HVAC systems throughout Europe [8]. Another example is given by the structure of wireless sensors and actuators and cloud-based algorithms developed by Enerbrain to optimize the operation of HVAC systems, saving energy and improving indoor comfort [9]. The application of the radiator characteristic coefficients when installation and heat transfer conditions significantly differ from the EN 442 reference testing method may lead to significant errors on the estimation of heating consumption. As it is not possible, in real applications, to reproduce the reference installation and heat transfer conditions for water radiators, it is necessary to know the errors and the uncertainty contributions associated with the various heat cost allocation methods, due to the large variety of installation effects [10]. Several in-the-field works were carried out, concerning experimental analyses of heat allocation systems [11,12], focusing on the installation effects on the thermal output of water radiators due to different hydraulic connections, shelves, cavities and obstructions. This work deals with the experimental analysis of an indirect method for the evaluation of individual heat consumptions, carried out at the INRIM central heating system test facility [13]. The proposed method is based on the steady-state indirect estimation of radiator thermal power and exploits the results of the EcoThermo virtual flow sensor [14,15] to estimate the water flow rates Buildings 2017, 7, 20 3 of 19 circulating through each water radiator. Namely, the method allows evaluating the thermal energy exchanged by water radiators by measuring the opening time of radiator valves and by determining the water temperature at radiator outflow from the EcoThermo flow rate estimation, the indoor ambient temperature measurement, the radiator characteristic coefficients and the measurement of main water supply temperature. Although the radiator characteristic coefficients are used for the indirect thermal energy estimation, the proposed method does not rely on temperature measurement at the radiator surface, avoiding some of the drawbacks associated with the on-site installation. A sensitivity analysis of the measurement model of the heat cost allocation method has been carried out, pointing out the potential effects of the uncertainties associated with input quantities on thermal power estimation. As endorsed by the typical flow rate dependence of radiator thermal power and by the results of the sensitivity analysis, the accuracy of the EcoThermo virtual flow sensor, whose typical errors settle within 5%, is adequate for thermal power estimation. For instance, considering a water flow rate equal to 80 L/h, an uncertainty of 5% on flow rate estimation entails a corresponding uncertainty contribution on thermal power estimation of about 0.7%. The results provided by the heat cost allocation method were compared against a reference method, which gives the fractions of heating consumption, as obtained by means of direct heat meters installed on each water radiator. The installation effects associated with water radiators at the INRIM central heating system test facility, which affect the accuracy of any indirect method for thermal power estimation based on radiator characteristic coefficients, are considered by evaluating the deviation between reference direct heat metering and the EN 442 model applied to each water radiator in steady-state conditions. The sharing of thermal energy consumption obtained by the proposed allocation method was observed to be in good agreement (within a maximum deviation of about 10%) with the best indirect estimation of the fractions of heating consumption, which is based on the EN 442 model and takes into account the inherent installation effects that characterize the water radiators at the INRIM test facility. Furthermore, a comparison between the proposed heat cost allocation method and conventional HCAs has been carried out. 2. Thermal Power Exchanged by Water Radiators Whenever possible, the direct measurement of the thermal energy exchanged by a heat-conveying fluid, carried out by means of a flow meter, a pair of temperature sensors and a calculation unit (direct heat meter assembly), is preferable because of its inherent accuracy. However, in many applications, such as heat cost allocation in apartment buildings with vertical distribution pipework, the measurement of flow rate at each water radiator is not feasible both for cost and installation reasons. In these situations, indirect methods for thermal energy measurement, based on the analysis of the heat transfer from the radiator surface or the heat-conveying fluid to the surrounding environment, are often exploited. 2.1. The European Standard EN 442 The European Standard EN 442 [2,3] defines the measurement system and the procedure to characterize the heat emission of water radiators and gives the mathematical model that describes the functional dependence of the radiator thermal power from the temperature difference between water and air in proximity of the heat transfer surface. Such a model represents the basis for any indirect method for the assessment of the thermal energy exchanged by water radiators, since they implement the characteristic coefficients obtained according to the EN 442 standard. The model described by the EN 442 for the assessment of the thermal power exchanged by the heat-conveying fluid flowing through a radiator in steady-state conditions is expressed as follows: Q = K(T T ) (1) m a Buildings 2017, 7, 20 4 of 19 where Q is the thermal power exchanged by the radiator, T is the mean temperature of the fluid between the inlet and outlet sections of the radiator, T is the air temperature at a proper undisturbed distance from the heat transfer surface and K and n are the characteristic coefficients of the radiator. The EN 442 model can also be expressed in the following way: . . T T m a Q = Q (2) N50 where the characteristic coefficient Q is the radiator nominal thermal power, exchanged with N50 (T T ) = 50 C. m a The characteristic coefficients must be determined by regression analysis of experimental data, where measurements of Q and T T are obtained according to a well-defined procedure inside ( ) m a a suitable thermal chamber, compliant with specific requirements defined by the European Standard EN 442. Measurements are carried out in steady-state conditions, such that thermal power can be measured by direct heat metering techniques. The EN 442 defines the test method and specifies the technical requirements of the thermal chamber, fixing the convective and radiative heat transfer conditions between the water radiator under test and the room environment. Thus, the characteristic coefficients of the radiators are associated with a specific operating condition, and their use in real applications to estimate the radiator thermal power may lead to significant errors if the installation and heat transfer conditions of the radiator in the particular environment are sensibly different from the ones inside the thermal chamber. Many factors can significantly affect the accuracy of the thermal power estimation by means of the EN 442 characteristic coefficients; in particular, installation issues, like hydraulic piping connections to the water radiators and their positioning inside cavities or under shelves [12,16], may have a considerable impact on the accuracy of indirect thermal power estimation. Moreover, other influencing factors are worth being noticed, e.g., the painting of radiator surfaces, the huge variety of possible radiant properties of the surrounding bodies and configuration factors that can characterize the installation of the radiator in a particular room, the presence of entrained and dissolved air and the accumulation of impurities, mud or metallic residuals inside the radiator. The possible onset of these factors in real operating conditions determines a variation of the characteristic coefficients of water radiators with respect to those associated with the installation in the thermal chamber as described by the EN 442. 2.2. The INRIM Central Heating System Test Facility A test facility to evaluate the performance of heat cost allocation methods for apartment buildings has been realized at INRIM, the Italian National Metrology Institute, in 2014 [13]. The test facility consists of a full-scale central heating system with 40 water radiators characterized by different shapes, hydraulic connections, dimensions and materials. The thermal-hydraulic network is automatically reconfigurable, in order to reproduce the desired topology of the circuit, and reference direct heat meters are installed on each water radiator to measure the thermal energy exchanged by the heat conveying fluid. Every reference direct heat meter consists of an electromagnetic flow meter, two Pt100 temperature sensors and a thermal energy calculation unit directly implemented on the PC, which receives the converted measurement signals from a Programmable Logic Controller (PLC). The uncertainties associated with the flow rate and temperature measurement chains are listed in Table 1 for a particular heat meter assembly. Buildings 2017, 7, 20 5 of 19 Table 1. Uncertainties of temperature and flow rate measurement chains for a particular heat meter assembly at the INRIM central heating system test facility. Expanded Uncertainty Range (95% conf.int.) Temperature measurement chain from 0 C to 90 C 0.06 C (Pt100 sensor, 4-wire shielded cable, PLC module) Electromagnetic flow meter from 90 L/h to 1800 L/h 0.2% (of the measured value) Buildings 2017, 7, 20 5 of 19 The uncertainty of thermal power measurement, as given by the reference direct heat meters, The uncertainty of thermal power measurement, as given by the reference direct heat meters, results from the propagation of the uncertainties associated with the input quantities through the results from the propagation of the uncertainties associated with the input quantities through the measurement model; it takes into account the stability of measurements at the test facility and the measurement model; it takes into account the stability of measurements at the test facility and the uncertainty related to the equation of state for the estimation of the thermodynamic properties of uncertainty related to the equation of state for the estimation of the thermodynamic properties of water [17,18]. The Monte Carlo method has been used to evaluate the uncertainty associated with water [17,18]. The Monte Carlo method has been used to evaluate the uncertainty associated with thermal power measurements provided by the reference direct heat meters [19]; Figure 1 shows the thermal power measurements provided by the reference direct heat meters [19]; Figure 1 shows the dependence of the relative standard uncertainty of thermal power measurement with respect to the dependence of the relative standard uncertainty of thermal power measurement with respect to the inlet-outlet inlet-outlet w water ater tem temperatur perat eure difd fer ifferenc ence, e, for foa r a particular particular d dir irect he ect heat at met meter er of of ththe e test f test acili facility ty. . Figure 1. Relative standard uncertainty associated with the thermal power measurement of a Figure 1. Relative standard uncertainty associated with the thermal power measurement of a particular particular reference direct heat meter at the INRIM central heating system test facility. reference direct heat meter at the INRIM central heating system test facility. The sub-assemblies of the reference direct heat meters, installed on each water radiator of the The sub-assemblies of the reference direct heat meters, installed on each water radiator of the test test facility, are periodically calibrated in order to ensure the metrological traceability to the facility correspo , are periodically nding reference calibrated standar in ds or . der to ensure the metrological traceability to the corresponding The laboratory allows testing heat cost allocation methods by comparing their results, in terms reference standards. of fractions of thermal energy consumption, with the ones provided by the reference direct heat The laboratory allows testing heat cost allocation methods by comparing their results, in terms of meters. Since the experimental conditions are significantly different from the ones of the thermal fractions of thermal energy consumption, with the ones provided by the reference direct heat meters. chamber, where radiators have been characterized according to the EN 442 standard, it is necessary Since the experimental conditions are significantly different from the ones of the thermal chamber, to evaluate the installation effects on each water radiator at the INRIM test facility, in order to where radiators have been characterized according to the EN 442 standard, it is necessary to evaluate provide significant experimental analyses for any indirect method for heat accounting. Along this the installation effects on each water radiator at the INRIM test facility, in order to provide significant line, the thermal power exchanged by each water radiator of the heating system is estimated in experimental analyses for any indirect method for heat accounting. Along this line, the thermal power steady-state conditions by means of the EN 442 model, using the characteristic coefficients obtained exchanged by each water radiator of the heating system is estimated in steady-state conditions by at the thermal chamber during the radiator characterization, the water temperature measurements at the inlet and outlet flow sections of the radiator and the air temperature measurement at a distance means of the EN 442 model, using the characteristic coefficients obtained at the thermal chamber of 1.5 m from the center of the radiator surface. The resulting relative deviation from the reference during the radiator characterization, the water temperature measurements at the inlet and outlet flow direct measurement of thermal power gives an assessment of the installation effects associated with sections of the radiator and the air temperature measurement at a distance of 1.5 m from the center of the particular water radiator (an example is given in Figure 2). the radiator surface. The resulting relative deviation from the reference direct measurement of thermal The evaluation of the installation effects that characterize the water radiators of the experimental thermal-hydraulic circuit is needed in order to assess the inherent limit of any indirect method for heat cost allocation when tested at the INRIM central heating system facility. Buildings 2017, 7, 20 6 of 19 power gives an assessment of the installation effects associated with the particular water radiator (an example is given in Figure 2). The evaluation of the installation effects that characterize the water radiators of the experimental thermal-hydraulic circuit is needed in order to assess the inherent limit of any indirect method for heat cost allocation when tested at the INRIM central heating system facility. Buildings 2017, 7, 20 6 of 19 (a) (b) Figure 2. Time evolution of: (a) reference thermal power measurement obtained by direct heat Figure 2. Time evolution of: (a) reference thermal power measurement obtained by direct heat metering and indirect thermal power estimation by the EN 442 model for a particular water radiator; metering and indirect thermal power estimation by the EN 442 model for a particular water radiator; (b) corresponding relative deviation between thermal power estimation by the EN 442 model and (b) corresponding relative deviation between thermal power estimation by the EN 442 model and reference direct heat metering. reference direct heat metering. 3. Characterization of the Proposed Heat Cost Allocation Method 3. Characterization of the Proposed Heat Cost Allocation Method A fair heat cost allocation in apartment buildings, where the individual thermal energy A fair heat cost allocation in apartment buildings, where the individual thermal energy consumptions can only be estimated indirectly by means of the semi-empirical relations associated consumptions can only be estimated indirectly by means of the semi-empirical relations associated with each water radiator according to the EN 442 model, is strongly dependent on: with each water radiator according to the EN 442 model, is strongly dependent on:  the correct identification of the thermal characteristics of each water radiator, the correct identification of the thermal characteristics of each water radiator,  the accurate evaluation of the temperature difference between the heat-conveying fluid flowing the accurate evaluation of the temperature difference between the heat-conveying fluid flowing through each radiator and the ambient air in proximity of the radiator surface. through each radiator and the ambient air in proximity of the radiator surface. While the identification of the characteristic coefficients of water radiators represents a common task for the heat cost allocation methods available on the market, the main difference between the While the identification of the characteristic coefficients of water radiators represents a common indirect solutions for the assessment of individual heat consumptions consists of how they estimate task for the heat cost allocation methods available on the market, the main difference between the or approximate the temperature difference between the heat-conveying fluid inside the radiator and indirect solutions for the assessment of individual heat consumptions consists of how they estimate the surrounding air. In particular, HCAs approximate the fluid-air temperature difference with the or approximate the temperature difference between the heat-conveying fluid inside the radiator measurement of the temperature difference between a specified point of the radiator surface and the and the surrounding air. In particular, HCAs approximate the fluid-air temperature difference with surrounding air temperature (close to the radiator surface). Such a temperature difference the measurement of the temperature difference between a specified point of the radiator surface measurement is properly corrected by suitable “coupling coefficients” that depend on the type of and the surrounding air temperature (close to the radiator surface). Such a temperature difference HCA (single sensor or double sensor) and the type of radiator on which the HCA is installed [6]. measurement is properly corrected by suitable “coupling coefficients” that depend on the type of Other heat cost allocation methods, like the ones based on insertion time counters [7], do not use HCA (single sensor or double sensor) and the type of radiator on which the HCA is installed [6]. temperature measurements at the radiator surface, but make proper approximations about the mean Other heat cost allocation methods, like the ones based on insertion time counters [7], do not use water temperature inside the radiators and the indoor air temperatures. temperature measurements at the radiator surface, but make proper approximations about the mean The heat cost allocation method proposed in this work allows assessing the individual fractions water temperature inside the radiators and the indoor air temperatures. of thermal energy consumption by means of:  the measurement of the opening time and opening degree of radiator valves,  the identification of the characteristic coefficients of each water radiator,  the measurements of the indoor air temperature at each living unit where the radiators are installed,  the measurement of the hot water supply temperature at the boiler room, Buildings 2017, 7, 20 7 of 19 The heat cost allocation method proposed in this work allows assessing the individual fractions of thermal energy consumption by means of: the measurement of the opening time and opening degree of radiator valves, the identification of the characteristic coefficients of each water radiator, the measurements of the indoor air temperature at each living unit where the radiators are installed, the measurement of the hot water supply temperature at the boiler room, the estimation of the water flow rate circulating through each water radiator, depending on the opening degree of radiator valves, the total water flow rate flowing through the thermal-hydraulic circuit and the overall hydraulic head loss. The EcoThermo virtual flow sensor provides the estimate of radiator volumetric flow rates, by solving the network model of the thermal-hydraulic circuit, whose branches are preliminarily identified in terms of head loss coefficients. 3.1. Measurement Model The measurement model adopted by the proposed method for the assessment of the thermal power exchanged by each water radiator, in steady-state conditions, can be described as follows: . . Q = Vrc (T T ) < p out in 1/n (3) Vrc T +T p out in = T + 50 (T T ) : a out in N50 In Equation (3), the input quantities of the model are the radiator characteristic coefficients Q N50 and n, the indoor air temperature measurement T near the radiator surface (air temperature measured in the living unit where the radiator is installed), the estimation of radiator water inlet temperature T (approximately equal to the hot water supply temperature at the boiler room) and the estimate of in water volumetric flow rate V passing through the radiator (which depends on the opening degree of the radiator valve). The solution of the measurement model, which is expressed in the form of a non-linear system of Equation (3), gives the estimation of the two unknowns: the thermal power Q and the water outlet temperature T of the radiator. Water density r and specific heat capacity c are functions of out p temperatures T and T and pressure, according to the water equation of state [17]; because of the out in slight pressure dependence of water thermodynamic properties within the thermal-hydraulic operating range of centralized heating systems, water density and specific heat capacity can be evaluated at a rough estimate of the mean absolute water pressure inside the thermal-hydraulic circuit. The thermal energy exchanged by the water radiator is obtained by the time integration of the thermal power during the opening time of the radiator valve. Figure 3 shows the dependence of the thermal power exchanged by a generic water radiator, in steady-state conditions, from the indoor air temperature and the water flow rate, as determined by the model described in Equation (3). The use of the steady-state model also for transient operating conditions, for instance when the radiator surface is warming up, can lead to the overestimation of the thermal power transferred to the surrounding environment, which is balanced out by the heat transfer occurring during the cooling down phase. Buildings 2017, 7, 20 7 of 19  the estimation of the water flow rate circulating through each water radiator, depending on the opening degree of radiator valves, the total water flow rate flowing through the thermal-hydraulic circuit and the overall hydraulic head loss. The EcoThermo virtual flow sensor provides the estimate of radiator volumetric flow rates, by solving the network model of the thermal-hydraulic circuit, whose branches are preliminarily identified in terms of head loss coefficients. 3.1. Measurement Model The measurement model adopted by the proposed method for the assessment of the thermal power exchanged by each water radiator, in steady-state conditions, can be described as follows: ̇ ̇ ( ) 𝑄 = 𝑉 𝜌 𝑐 𝑇 − 𝑇 𝑝 𝑜𝑢𝑡 ̇ (3) 𝑉 𝜌 𝑐 𝑇 + 𝑇 𝑜𝑢𝑡 𝑝 = 𝑇 + 50 [ (𝑇 − 𝑇 )] 𝑎 𝑜𝑢𝑡 2 𝑄 𝑁 50 In Equation (3), the input quantities of the model are the radiator characteristic coefficients 𝑄 and 𝑛 , the indoor air temperature measurement 𝑇 near the radiator surface (air temperature 𝑁 50 𝑎 measured in the living unit where the radiator is installed), the estimation of radiator water inlet temperature 𝑇 (approximately equal to the hot water supply temperature at the boiler room) and the estimate of water volumetric flow rate 𝑉 passing through the radiator (which depends on the opening degree of the radiator valve). The solution of the measurement model, which is expressed in the form of a non-linear system of Equation (3), gives the estimation of the two unknowns: the thermal power 𝑄 and the water outlet temperature 𝑇 of the radiator. Water density 𝜌 and specific heat capacity 𝑐 are functions 𝑜𝑢𝑡 𝑝 of temperatures 𝑇 and 𝑇 and pressure, according to the water equation of state [17]; because of 𝑜𝑢𝑡 the slight pressure dependence of water thermodynamic properties within the thermal-hydraulic operating range of centralized heating systems, water density and specific heat capacity can be evaluated at a rough estimate of the mean absolute water pressure inside the thermal-hydraulic circuit. The thermal energy exchanged by the water radiator is obtained by the time integration of the thermal power during the opening time of the radiator valve. Figure 3 shows the dependence of the thermal power exchanged by a generic water radiator, in steady-state conditions, from the indoor air temperature and the water flow rate, as determined by the model described in Equation Buildings 2017, 7, 20 8 of 19 (3). Figure 3. Dependence of radiator thermal power from indoor air temperature and water flow rate. 3.2. Sensitivity Analysis Measurements and estimations for indoor air temperature, hot water supply temperature, radiator characteristic coefficients and water flow rate circulating through the radiator are essential for the accurate evaluation of the temperature of the fluid at the outlet section of the radiator. Anyway, not the same degree of accuracy is required for the assessment of the mentioned quantities. In order to obtain a ranking of the input quantities of the measurement model in terms of influence on the estimated thermal power exchanged by the water radiator, a sensitivity analysis has been carried out. According to the measurement model described by the system of Equation (3), the output quantity thermal power can be expressed as a function of several input quantities: . . . . Q = Q(T , T , V, Q , n) (4) a in N50 The evaluation of the gradient of Q allows one to get useful information about the impact of each input quantity on thermal power, since the components of the gradient represent the sensitivity coefficients that characterize the allocation model: ( ) . . . . . ¶Q ¶Q ¶Q ¶Q ¶Q rQ = , , , , (5) . . ¶T ¶T ¶n in ¶V ¶Q N50 The gradientrQ has been evaluated numerically by changing one-factor-at-a-time (OFAT) at each point within the multi-dimensional space of the input variables of the model. Moreover, the gradient of the thermal power has been normalized to the thermal power itself, in order to get the relative variation of Q with respect to the unit variation of the input quantities. Table 2 shows the results of the analysis in terms of sensitivity coefficients associated with a specific point within the space of the input variables and an example of evaluation of the uncertainty budget resulting from typical uncertainties assigned to the input quantities. 𝑖𝑛 𝑖𝑛 𝑖𝑛 𝑖𝑛 𝑖𝑛 Buildings 2017, 7, 20 9 of 19 Table 2. Results of the sensitivity analysis and example of uncertainty budget for the proposed heat cost allocation model. Output Relative Input Standard Sensitivity Coefficient Standard Estimate Uncertainty PDF ¶Q 1 Uncertainty x . ¶x . . u(x ) u Q /Q Water inlet 65 C 0.5 C Uniform 2.97 1.48% temperature Indoor ambient 21 C 0.5 C Normal 2.93 1.47% temperature Water flow rate 80 L/h 4 L/h Uniform 0.18 0.72% L/h Radiator nominal thermal power 1400 W 100 W Uniform 0.06 5.95% (at DT = 50 C) Radiator exponent 1.35 (-) 0.1 (-) Uniform 21.54 2.15% (-) Because of the variety of installation and operating conditions for water radiators in real applications, a larger uncertainty has been assigned to the estimations of the radiator characteristic coefficients (higher than 7% for both the radiator nominal thermal power and the radiator exponent). As a consequence of the corresponding sensitivity coefficients, the uncertainty contributions on thermal power are, respectively, around 6% due to the radiator nominal thermal power and 2% due to the radiator exponent. Moreover, as endorsed by the results of the sensitivity analysis, a lower accuracy can be accepted for water flow rate estimation, while particular care should be taken for the evaluation of indoor air temperature and hot water inlet temperature. 3.3. Estimation of Water Flow Rates Circulating through the Radiators In order to estimate the water flow rates circulating through the radiators, the proposed heat cost allocation method uses the results of the soft-sensor EcoThermo, which is applied to the thermal-hydraulic network of the central heating system, where the water radiators are installed. The EcoThermo soft-sensor has been developed and tested in the context of the EU 7thFramework Program for Small and Medium-sized Enterprises FP7-SME-2012 “Innovative green technology for smart energy saving on existing residential buildings with centralized heating/cooling generators” [14]. It is based on the network modelling of the thermal-hydraulic circuit of a generic central heating system, where the hydraulic characteristics (head loss coefficients) of each branch are preliminarily estimated by means of a suitable algorithm for the mathematical identification of the network. The procedure for the mathematical identification of the hydraulic circuit is the core of EcoThermo and consists of the characterization of the minimum number of hydraulic subsystems in which the network can be divided. Namely, the head loss coefficients of each subsystem or closed branch are estimated by non-linear regression of the measurements of water flow rate and corresponding head loss, respectively provided by a fixed volumetric flow meter and two pressure transducers installed at the main supply and return pipe flows in the boiler room. The mathematical relation used to describe the dependence between head loss D p and volumetric flow rate V in a generic branch of the hydraulic network can be expressed as follows: D p = aV (6) where a and b are the characteristic hydraulic coefficients of the branch. The use of a suitable pump equipped with an inverter or other flow rate control systems is necessary in order to generate a representative set of water flow rates and head losses for the hydraulic characterization of the branches. Buildings 2017, 7, 20 10 of 19 Once the hydraulic circuit has been identified, the water volumetric flow rates circulating through each open radiator can be estimated from the overall volumetric flow rate and head loss measurements at the main pipe flow, by solving the network model. The EcoThermo soft-sensor has been validated at the INRIM central heating system test facility, in a wide set of network topologies and operating conditions [14,15]. Figure 4 shows an example of the results obtained by EcoThermo for the estimation of the water flow rate through a particular radiator of the thermal-hydraulic circuit. Buildings 2017, 7, 20 10 of 19 (a) (b) Figure 4. Time evolution of: (a) EcoThermo flow rate estimation and reference water flow rate Figure 4. Time evolution of: (a) EcoThermo flow rate estimation and reference water flow rate measurement at a particular radiator; (b) corresponding relative error of EcoThermo estimation with measurement at a particular radiator; (b) corresponding relative error of EcoThermo estimation with respect to reference water flow rate measurement. respect to reference water flow rate measurement. The soft-sensor EcoThermo could also be used as an effective tool for the optimal management The soft-sensor EcoThermo could also be used as an effective tool for the optimal management of of central heating systems; for instance, it could enable the dynamic balancing of the hydraulic central heating systems; for instance, it could enable the dynamic balancing of the hydraulic circuit, circuit, preventing either too high or too low flow rates at each water radiator. Moreover, it could preventing either too high or too low flow rates at each water radiator. Moreover, it could ensure that ensure that radiator valves operate with a stable and predictable hydraulic response, in terms of radiator valves operate with a stable and predictable hydraulic response, in terms of fixed dependence fixed dependence between water flow rate and opening degree. between water flow rate and opening degree. 4. Results of the Experimental Analysis 4. Results of the Experimental Analysis The proposed heat cost allocation method has been tested at the INRIM central heating system The proposed heat cost allocation method has been tested at the INRIM central heating system test facility, where each water radiator is equipped with a reference direct heat meter for thermal test facility, where each water radiator is equipped with a reference direct heat meter for thermal energy measurement. A set of 11 water radiators, which consists of 7 aluminum, 2 cast iron and energy measurement. A set of 11 water radiators, which consists of 7 aluminum, 2 cast iron and 2 tubular steel radiators distributed on four different risers, as shown in Figure 5, has been selected 2 tubular steel radiators distributed on four different risers, as shown in Figure 5, has been selected for for the tests. the tests. Buildings 2017, 7, 20 11 of 19 Buildings 2017, 7, 20 11 of 19 Figure 5. Scheme of the thermal-hydraulic circuit of the INRIM test facility and selected set of Figure 5. Scheme of the thermal-hydraulic circuit of the INRIM test facility and selected set of waterwater rad radiators. iators. The pump and the heater have been programmed to feed the 11 radiators of the The pump and the heater have been programmed to feed the 11 radiators of the thermal-hydraulic thermal-hydraulic circuit with the desired water flow rate and temperature, and the motorized circuit with the desired water flow rate and temperature, and the motorized radiator valves have been radiator valves have been automatically controlled to set the desired opening/closing times. The task automatically controlled to set the desired opening/closing times. The task for the heat cost allocation for the heat cost allocation method is to provide the individual fractions of thermal energy method is to provide the individual fractions of thermal energy consumption for each water radiator, consumption for each water radiator, defined as: defined as: 𝑓 = 𝑖 (7) f = (7) 11 𝑗 𝑗 =1 j=1 where 𝑄 is the thermal energy exchanged by the i-th water radiator, calculated by the time where Q is the thermal energy exchanged by the i-th water radiator, calculated by the time integration integration of the thermal power estimated by means of the model described by the system of of the thermal power estimated by means of the model described by the system of Equation (3). Equation (3). The characteristic thermal coefficients of water radiators, which are used by the The characteristic thermal coefficients of water radiators, which are used by the allocation method to allocation method to estimate the individual thermal energy consumptions, are obtained from the estimate the individual thermal energy consumptions, are obtained from the radiator datasheets and radiator datasheets and are listed in Table 3. are listed in Table 3. Table 3. Characteristic coefficients of water radiators. Nominal Thermal Exponent Power at DT = 50 C Q (W) N50 Aluminum radiators 1467 1.359 Cast iron radiators 1427 1.3679 Tubular steel radiators 1482 1.28 The proposed method has been tested by evaluating, for each water radiator, the deviation between the estimated fraction of thermal energy consumption and the one measured by the reference direct heat meters. The relative deviations from the reference measurements of the individual fractions of heat consumption ( f ) can be expressed as follows: i,REF f f i i,REF # = (8) i,REF Moreover, the heat cost allocation method has been compared against conventional HCAs installed on the set of selected radiators (Figure 6), based on the relative deviations from the reference fractions of heat consumption provided by direct heat meters. HCAs have been programmed using the radiator Buildings 2017, 7, 20 12 of 19 Table 3. Characteristic coefficients of water radiators. Nominal Thermal Exponent Power at ΔT = 50 °C 𝑸 (W) 𝑵𝟓𝟎 Aluminum radiators 1467 1.359 Cast iron radiators 1427 1.3679 Tubular steel radiators 1482 1.28 The proposed method has been tested by evaluating, for each water radiator, the deviation between the estimated fraction of thermal energy consumption and the one measured by the reference direct heat meters. The relative deviations from the reference measurements of the individual fractions of heat consumption (𝑓 ) can be expressed as follows: 𝑖 ,𝑅𝐸𝐹 𝑓 − 𝑓 𝑖 𝑖 ,𝑅𝐸𝐹 𝜀 = (8) 𝑖 ,𝑅𝐸𝐹 Buildings 2017, 7, 20 12 of 19 Moreover, the heat cost allocation method has been compared against conventional HCAs installed on the set of selected radiators (Figure 6), based on the relative deviations from the reference fractions of heat consumption provided by direct heat meters. HCAs have been characteristic coefficients listed in Table 3 and the rating factors for the device-radiator coupling programmed using the radiator characteristic coefficients listed in Table 3 and the rating factors for provided by the manufacturer, according to the EN 834 standard [6]. the device-radiator coupling provided by the manufacturer, according to the EN 834 standard [6]. Figure 6. Experimental setup at the INRIM central heating system test facility. Figure 6. Experimental setup at the INRIM central heating system test facility. The indoor air temperature measurements, which are needed by the proposed heat cost allocation method to estimate the fractions of thermal energy consumption, are provided by five The indoor air temperature measurements, which are needed by the proposed heat cost allocation Pt100 temperature sensors placed at different heights, corresponding to the position of water method to estimate the fractions of thermal energy consumption, are provided by five Pt100 radiators on the risers, at about 1.5 m from the nearest heating surfaces (Figure 6). temperature sensors placed at different heights, corresponding to the position of water radiators Furthermore, the indoor air temperature measurements are used to evaluate the individual on the risers, at about 1.5 m from the nearest heating surfaces (Figure 6). fractions of thermal energy consumption by means of the EN 442 model. Such a model, in addition Furthermore, the indoor air temperature measurements are used to evaluate the individual to the indoor air temperature measurements and the characteristic thermal coefficients of each fractions of thermal energy consumption by means of the EN 442 model. Such a model, in addition to radiator, uses the reference temperature sensors directly immersed at the inlet and outlet flow the indoor air temperature measurements and the characteristic thermal coefficients of each radiator, sections of each water radiator to evaluate the water mean temperatures. As discussed in Section 2.2, uses the reference temperature sensors directly immersed at the inlet and outlet flow sections of each the comparison between the indirect estimation of radiator thermal power by means of the EN 442 water mo radiator del and to the evaluate reference the direct water meas mean uremen temperatur t of the thermal es. As po discussed wer exchange in Section d by the 2.2 heat , the -conv compari eying son fluid passing through the radiator in steady-state conditions allows one to evaluate the uncertainty between the indirect estimation of radiator thermal power by means of the EN 442 model and the reference direct measurement of the thermal power exchanged by the heat-conveying fluid passing through the radiator in steady-state conditions allows one to evaluate the uncertainty contribution due to the particular installation and operating conditions in the laboratory during the tests. As well as in real applications, the installation and operating conditions at the INRIM central heating system may be significantly different from the ones to which the characteristic thermal coefficients of the radiators refer. For this reason, the performance of any heat cost allocation method based on the EN 442 model must take into account the inherent limit due to the particular installation and operating conditions at the test facility, which is highlighted by the deviation between the individual heat consumptions provided by the EN 442 model and the reference direct heat metering in steady-state conditions. A Pt100 temperature sensor directly immersed in the main hot water supply flow exiting from the heater gives the estimation of radiator inlet temperatures, which are needed by the heat cost allocation method to evaluate the fractions of thermal energy consumption. Such an approximation is justified, in real applications, by the economic and practical constraints related to the installation of thermometers at the inlet sections of each water radiator of the central heating system. The experiments for testing the proposed heat cost allocation method are characterized by the following operating conditions: Balanced hydraulic network: the thermal-hydraulic circuit of the central heating system has been preliminarily balanced, as should be recommended in real applications, in order to obtain a uniform flow rate distribution among the water radiators; Buildings 2017, 7, 20 13 of 19 contribution due to the particular installation and operating conditions in the laboratory during the tests. As well as in real applications, the installation and operating conditions at the INRIM central heating system may be significantly different from the ones to which the characteristic thermal coefficients of the radiators refer. For this reason, the performance of any heat cost allocation method based on the EN 442 model must take into account the inherent limit due to the particular installation and operating conditions at the test facility, which is highlighted by the deviation between the individual heat consumptions provided by the EN 442 model and the reference direct heat metering in steady-state conditions. A Pt100 temperature sensor directly immersed in the main hot water supply flow exiting from the heater gives the estimation of radiator inlet temperatures, which are needed by the heat cost allocation method to evaluate the fractions of thermal energy consumption. Such an approximation is justified, in real applications, by the economic and practical constraints related to the installation of thermometers at the inlet sections of each water radiator of the central heating system. The experiments for testing the proposed heat cost allocation method are characterized by the following operating conditions: Buildings 2017, 7, 20 13 of 19  Balanced hydraulic network: the thermal-hydraulic circuit of the central heating system has been preliminarily balanced, as should be recommended in real applications, in order to obtain Automatic control of the opening/closing time of radiator valves: the motorized supply valves a uniform flow rate distribution among the water radiators; of the 11 water radiators, which can only set on their fully-open/closed state, are preliminarily  Automatic control of the opening/closing time of radiator valves: the motorized supply valves programmed in terms of opening/closing times, simulating typical daily occupancy behaviors, of the 11 water radiators, which can only set on their fully-open/closed state, are preliminarily as shown in Figure 7; programmed in terms of opening/closing times, simulating typical daily occupancy behaviors, Constant as shown water in Figur supply e 7; temperature and constant pump speed: the heater is set to ensure  Constant water supply temperature and constant pump speed: the heater is set to ensure a a constant hot water supply temperature of 65 C, and the pump is set to operate at 45% of constant hot water supply temperature of 65 °C, and the pump is set to operate at 45% of its its maximum speed; maximum speed; Cooling down of radiator surfaces: the tests include the time needed for the complete natural  Cooling down of radiator surfaces: the tests include the time needed for the complete natural cooling down of the heat transfer surface of radiators after either the closing of radiator valves or cooling down of the heat transfer surface of radiators after either the closing of radiator valves the shutdown of the heater; this is necessary in order to compare the heat cost allocation obtained or the shutdown of the heater; this is necessary in order to compare the heat cost allocation by means of HCAs and the EN 442 model, with the one provided by reference direct heat meters; obtained by means of HCAs and the EN 442 model, with the one provided by reference direct Long heat met time duration ers; of the tests: the tests are characterized by long-time recording, such that the  Long time duration of the tests: the tests are characterized by long-time recording, such that the resolution error of the 11 HCAs becomes negligible if compared to the corresponding amount of resolution error of the 11 HCAs becomes negligible if compared to the corresponding amount totalized units of heating consumption. of totalized units of heating consumption. Figure 7. Programmed daily opening time of radiator valves. Figure 7. Programmed daily opening time of radiator valves. In such an experimental test condition, the estimations of the fractions of heating consumption associated with each water radiator, as given by the proposed heat cost allocation method, have been compared to the ones provided by the reference direct heat meters. In order to take into account the installation effects that characterize the particular operation of water radiators at the INRIM test facility, the individual fractions of thermal energy consumption have been evaluated also by means of the EN 442 model. It is worth noticing how the operating conditions designed for the test may deviate from what usually happens in real applications. For instance, balanced hydraulic networks, although recommended, are not so typical for old buildings, while the control of supply temperature, pump speed and radiator valves may be affected by hysteresis and communication issues or can be designed with different criteria, e.g., supply temperature and flow can be controlled by external ambient temperature measurement. Moreover, the ON-OFF operation of water radiators, as programmed for the test, is getting more and more unusual in current applications, because of the growing use of thermostatic radiator valves, which allows modulating the radiator thermal power according to the desired indoor air temperature. Figure 8 shows the time trend of the indoor air temperature measurements during the test, as given by the five Pt100 thermometers installed at different heights inside the laboratory in proximity of the heating surfaces of the radiators. The time evolution follows the programmed opening/closing times Buildings 2017, 7, 20 14 of 19 In such an experimental test condition, the estimations of the fractions of heating consumption associated with each water radiator, as given by the proposed heat cost allocation method, have been compared to the ones provided by the reference direct heat meters. In order to take into account the installation effects that characterize the particular operation of water radiators at the INRIM test facility, the individual fractions of thermal energy consumption have been evaluated also by means of the EN 442 model. It is worth noticing how the operating conditions designed for the test may deviate from what usually happens in real applications. For instance, balanced hydraulic networks, although recommended, are not so typical for old buildings, while the control of supply temperature, pump speed and radiator valves may be affected by hysteresis and communication issues or can be designed with different criteria, e.g., supply temperature and flow can be controlled by external ambient temperature measurement. Moreover, the ON-OFF operation of water radiators, as programmed for the test, is getting more and more unusual in current applications, because of the growing use of thermostatic radiator valves, which allows modulating the radiator thermal power according to the desired indoor air temperature. Figure 8 shows the time trend of the indoor air temperature measurements during the test, as given by the five Pt100 thermometers installed at different heights inside the laboratory in proximity of the heating surfaces of the radiators. The time evolution follows the programmed opening/closing Buildings 2017, 7, 20 14 of 19 times of water radiators and highlights the vertical stratification of air temperatures inside the laboratory. Indoor air temperature has been observed ranging from about 18 °C (at a 1-m height of water radiators and highlights the vertical stratification of air temperatures inside the laboratory. from the floor) to a maximum of about 25 °C (at a 3-m height from the floor). Although the air temperature measurement points are equally spaced on the height of the laboratory, a slightly Indoor air temperature has been observed ranging from about 18 C (at a 1-m height from the floor) to stronger thermal stratification was observed between the second and third floors, with respect to the a maximum of about 25 C (at a 3-m height from the floor). Although the air temperature measurement first and points are equally spaced on the height of the laboratory, a slightly stronger thermal stratification was second ones. observed between the second and third floors, with respect to the first and second ones. Figure 8. Time evolution of indoor air temperature measurements during the test. Figure 8. Time evolution of indoor air temperature measurements during the test. Figure 9 shows the results of the test in terms of fractions of thermal energy consumption, as Figure 9 shows the results of the test in terms of fractions of thermal energy consumption, as given given by the reference direct heat meters, the EN 442 model applied to each water radiator, the by the reference direct heat meters, the EN 442 model applied to each water radiator, the HCAs and HCAs and the proposed heat cost allocation method. The last, as described in Section 3.3, exploits the proposed heat cost allocation method. The last, as described in Section 3.3, exploits the results of the results of the EcoThermo soft-sensor to estimate the water flow rates circulating through each Buildings 2017, 7, 20 15 of 19 the EcoThermo water radiato soft-sensor r. to estimate the water flow rates circulating through each water radiator. Figure 9. Fractions of heating consumption associated with water radiators. HCA, Heat Cost Allocator. Figure 9. Fractions of heating consumption associated with water radiators. HCA, Heat Cost Allocator. All of the heat cost allocation methods, as well as reference direct heat metering, provide greater All of the heat cost allocation methods, as well as reference direct heat metering, provide fractions of heat consumption for second floor radiators (N13, N14, N15, S11), which are open for greater fractions of heat consumption for second floor radiators (N13, N14, N15, S11), which are a longer time (16 h/day). Focusing on radiators N20 and N10 (same material, shape and dimension), open for a longer time (16 h/day). Focusing on radiators N20 and N10 (same material, shape and which are installed on the same riser at the first and third floors, respectively, and are characterized by dimension), which are installed on the same riser at the first and third floors, respectively, and are almost the same feeding flow rate and the same opening time (8 h/day), it can be observed that the characterized by almost the same feeding flow rate and the same opening time (8 h/day), it can be reference fractions of heat consumption are lower for radiator N10 than for N20 (about 6% for radiator observed that the reference fractions of heat consumption are lower for radiator N10 than for N20 N10 (a and bout 7% 6% for forN20), radiator mainly N10 and because 7% for of N20) indoor , mainly b air temperatur ecause of inde oor stratification. air temperature The strsame atification. behavior The same behavior cannot be observed for the heat cost allocation provided by indirect methods, cannot be observed for the heat cost allocation provided by indirect methods, like the EN 442 model like the EN 442 model and HCAs, since their estimates are significantly affected by installation effects, and the fractions of heating consumptions are strongly correlated. The proposed heat cost allocation method is sensitive to installation effects, as well, but the evaluation of the heat output only when the radiator valve is open could slightly improve or decrease the accuracy of the estimated fractions of heat consumption, depending on the frequency of the ON-OFF operation of radiator valves and on the uniformity of installation effects. Moreover, while the accuracy of radiator characteristic coefficients is ensured for describing the heat transfer occurring when water is flowing through the radiator, their use for the estimation of the thermal power transferred from the hot surface to the surrounding air when the radiator valve is closed may lead to errors that cannot be related, exclusively, to installation effects. The relative deviations between the individual fractions of heating consumption and the reference ones have been evaluated for the EN 442 model, the HCAs and the proposed allocation method, and the results are shown in Figure 10. The sharing of thermal energy consumption provided by the proposed allocation method reproduces quite accurately the heat cost allocation obtained by means of the EN 442 model, with slight differences due to the evaluation of radiator thermal power only during the opening time of the corresponding valves and to the assumptions made for estimating the water inlet temperatures and flow rates at each radiator. Such deviations between the proposed heat cost allocation method and the EN 442 model settle within 10% and are greater for third floor radiators (N10, N9, N8 and S6), because of the more frequent ON-OFF operation for such heat delivery points. The contribution of the inherent installation effects that characterize the radiators at the central heating system test facility is such that the relative deviations of the EN 442 model, with respect to the reference fractions of heating consumption, vary within ±10% for most of the radiators, except for radiators N18 and N19, characterized by relative deviations of about −15% and −13%, respectively. As far as the proposed heat cost allocation method is concerned, the modulus of the maximum relative deviation from the reference fraction of heat consumption Buildings 2017, 7, 20 15 of 19 and HCAs, since their estimates are significantly affected by installation effects, and the fractions of heating consumptions are strongly correlated. The proposed heat cost allocation method is sensitive to installation effects, as well, but the evaluation of the heat output only when the radiator valve is open could slightly improve or decrease the accuracy of the estimated fractions of heat consumption, depending on the frequency of the ON-OFF operation of radiator valves and on the uniformity of installation effects. Moreover, while the accuracy of radiator characteristic coefficients is ensured for describing the heat transfer occurring when water is flowing through the radiator, their use for the estimation of the thermal power transferred from the hot surface to the surrounding air when the radiator valve is closed may lead to errors that cannot be related, exclusively, to installation effects. The relative deviations between the individual fractions of heating consumption and the reference ones have been evaluated for the EN 442 model, the HCAs and the proposed allocation method, and the results are shown in Figure 10. The sharing of thermal energy consumption provided by the proposed allocation method reproduces quite accurately the heat cost allocation obtained by means of the EN 442 model, with slight differences due to the evaluation of radiator thermal power only during the opening time of the corresponding valves and to the assumptions made for estimating the water inlet temperatures and flow rates at each radiator. Such deviations between the proposed heat cost allocation method and the EN 442 model settle within 10% and are greater for third floor radiators (N10, N9, N8 and S6), because of the more frequent ON-OFF operation for such heat delivery points. The contribution of the inherent installation effects that characterize the radiators at the central heating system test facility is such that the relative deviations of the EN 442 model, with respect to the reference fractions of heating consumption, vary within 10% for most of the radiators, except for Buildings 2017, 7, 20 16 of 19 radiators N18 and N19, characterized by relative deviations of about 15% and 13%, respectively. does not As far as the proposed heat cost allocation method is concerned, the modulus of the maximum relative exceed 11%. deviation from the reference fraction of heat consumption does not exceed 11%. Figure 10. Relative deviations from reference measurements of individual fractions of Figure 10. Relative deviations from reference measurements of individual fractions of heating consumption. heating consumption. On the other hand, the heat cost allocation obtained by means of HCAs describes a scenario On the other hand, the heat cost allocation obtained by means of HCAs describes a scenario of of individual fractions of thermal energy consumption that is very different from the actual one, individual fractions of thermal energy consumption that is very different from the actual one, with with relative deviations with respect to reference heat cost allocation up to about 30%. This may be due relative deviations with respect to reference heat cost allocation up to about 30%. This may be due to to the thdif e different ferent types types of of mounting mounting adopt adopted ed for forth the e inst installation allation of of HCA HCAs s on th on e the diffe dif rent fer typ ent es types of water of water radiators used for the test. In fact, while the same type of installation is more likely to result in the radiators used for the test. In fact, while the same type of installation is more likely to result in the same accuracy on the estimation of individual heat consumptions, the different mountings of HCAs same accuracy on the estimation of individual heat consumptions, the different mountings of HCAs in in the same heating system may entail large errors in terms of fractions of thermal energy the same heating system may entail large errors in terms of fractions of thermal energy consumption. consumption. In order to evaluate this effect, the heat cost allocation has been carried out In order to evaluate this effect, the heat cost allocation has been carried out considering only the seven considering only the seven aluminum radiators of the selected set, characterized by the same mounting installation of the HCA on the radiator surface. The results in terms of relative deviations from the reference fractions of thermal energy consumption are shown in Figure 11. Buildings 2017, 7, 20 16 of 19 does not exceed 11%. Figure 10. Relative deviations from reference measurements of individual fractions of heating consumption. On the other hand, the heat cost allocation obtained by means of HCAs describes a scenario of individual fractions of thermal energy consumption that is very different from the actual one, with relative deviations with respect to reference heat cost allocation up to about 30%. This may be due to the different types of mounting adopted for the installation of HCAs on the different types of water radiators used for the test. In fact, while the same type of installation is more likely to result in the same accuracy on the estimation of individual heat consumptions, the different mountings of HCAs Buildings 2017, 7, 20 16 of 19 in the same heating system may entail large errors in terms of fractions of thermal energy consumption. In order to evaluate this effect, the heat cost allocation has been carried out considering only the seven aluminum radiators of the selected set, characterized by the same aluminum radiators of the selected set, characterized by the same mounting installation of the HCA on mounting installation of the HCA on the radiator surface. The results in terms of relative deviations the radiator surface. The results in terms of relative deviations from the reference fractions of thermal from the reference fractions of thermal energy consumption are shown in Figure 11. energy consumption are shown in Figure 11. Figure 11. Relative deviations from reference measurements of individual fractions of heating consumption, only for the aluminum radiators (cast iron and steel radiators have been excluded for the assessment of heat cost allocation). A significant reduction of the relative deviations in particular for HCAs at radiators N10, N9, N8 and S6 can be observed. This is due to the uniformity of the types of mounting installation and to the correlation between the fractions of heating consumption. The maximum relative deviation with respect to the reference heat cost allocation obtained by direct heat meters is about 15% for HCAs (radiator N10), while, as far as the proposed allocation method is concerned, the relative deviations settle within 6% for all seven aluminum radiators. Moreover, it is worth noticing that HCAs and the EN 442 model, unlike both the reference direct heat meters and the proposed heat cost allocation method, are able to detect the heat transfer from the radiator surface, even when the water flow rate is not circulating through the radiator. This may happen either when the radiator valve closes and the stagnant hot water remains inside the radiator tubes or when a closed radiator is connected to a riser in which hot water is circulating because of the presence of at least one open radiator; in such a case, depending on the piping connections of the hydraulic circuit and the position of the closed radiator with respect to the open ones, heat is transferred by conduction from the hot riser to the closed radiator (through the pipe wall and the stagnant water). While the additional heat transfer, which occurs because of the presence of stagnant hot water inside a closed radiator, is balanced out by the smaller thermal power transferred to the surrounding air during the warming up of the radiator surface, the heat conduction from the risers behaves as an offset. In order to compare the fractions of heating consumption provided by the EN 442 model with the ones obtained by both the reference direct heat meters and the proposed allocation method, the heat cost allocation evaluated by the EN 442 model has been carried out excluding the contribution due to heat conduction from the risers when the water flow rate is not circulating through the radiators. Such a correction is taken into account since the contribution due to the heat conduction from the hot risers, when the radiator valve is closed, should not be considered as a voluntary individual thermal energy consumption. As far as the heat cost allocation provided by HCAs is concerned, the heat conduction contribution should be taken into account within the uncertainty budget associated with the estimated fractions of heating consumption, since it is not possible to correct the readings of Buildings 2017, 7, 20 17 of 19 each HCA, by separating the heat conduction contribution from the total amount of units of thermal energy consumption. 5. Conclusions The method described in this work, for heat accounting in apartment buildings, has provided good results in terms of accuracy on the estimation of individual fractions of thermal energy consumptions, as pointed out by the preliminary experimental analysis carried out at the INRIM central heating system test facility. The sharing of heat consumption evaluated by the proposed method has been observed to be very close to the heat cost allocation provided by the EN 442 model (within a maximum deviation of about 10%), which has been calculated using the characteristic radiator coefficients, the reference inlet and outlet water temperature measurements for each radiator and the air temperature measurements in proximity of the heat transfer surfaces. The contribution of the installation effects that characterize the radiators at the INRIM central heating system test facility is such that the relative deviations between the fractions of heat consumption provided by the EN 442 model and the reference ones given by direct heat meters vary within 10% for most of the radiators, except for two radiators of the set, characterized by relative deviations of about 15% and 13%. The results of the test show that the proposed method is mainly affected by the inherent installation effects that characterize the test facility, endorsing the effectiveness of the measurement model for the estimation of individual thermal energy consumptions. The approach adopted by the proposed heat cost allocation method, consisting of the evaluation of thermal power only when the radiator valve is open, could slightly improve or decrease the accuracy of the estimated fractions of heat consumption, depending on the frequency of the ON-OFF operation of radiator valves and on the uniformity of installation effects. Moreover, it could avoid possible errors that may result from the application of radiator characteristic coefficients to the evaluation of the exchanged thermal power when water is not flowing through the radiator. The assumptions made for the approximation of water inlet temperatures of radiators and the use of the EcoThermo soft-sensor for the estimation of radiator flow rates do not entail a significant reduction of the accuracy of the heat cost allocation method, as predicted by the sensitivity analysis. The modulus of the maximum relative deviation from the reference fraction of heating consumption does not exceed 11%. The proposed method has been compared also with conventional HCAs, and the results of the test have pointed out the importance of ensuring homogeneous mounting installations of these devices on the set of water radiators selected for the test. Namely, the different mounting adopted for tubular steel radiators, with respect to aluminum and cast iron radiators, has led to significant deviations from reference fractions of heat consumption, even up to 30%. In order to verify the effect of the mounting installation on the accuracy of HCAs, the heat cost allocation has been carried out considering only the seven aluminum radiators of the selected set, characterized by the same mounting of HCAs on radiator surfaces. A significant reduction of the relative deviations with respect to the reference fractions of heating consumptions has been observed; namely, a maximum deviation of about 15% has been obtained for HCAs, while, regarding the proposed allocation method, the relative deviations settled within 6% for all seven aluminum radiators. As far as the in-the-field application is concerned, the proposed indirect method for heat accounting is safe from some of the installation effects that may affect the accuracy of HCAs, like the on-site mounting of the devices and the identification of the radiator-device coupling coefficients, since it does not rely on the temperature measurement of the radiator external surface. Moreover, in order to ensure the correct application of the heat cost allocation model and the effective use of the EcoThermo soft-sensor, the signals related to the state (opening degree) and opening time of radiator valves, indoor air temperatures, hot water supply temperature, total flow rate and overall head loss, must be transmitted to a suitable data acquisition system and logged at a proper sampling time. Furthermore, it is worth observing that the deviations between the fractions of heating consumption obtained by indirect heat cost allocation methods and the reference ones provided Buildings 2017, 7, 20 18 of 19 by direct heat meters can also be influenced by the capability of indirect methods to assess the radiator heat transfer even if no water is circulating. For such a reason, the tests have been carried out either by comparing direct and indirect methods in steady-state operating conditions only or by considering test durations that ensure the indirect estimation of radiator thermal power to balance out the symmetric warming up and cooling down transients. Moreover, as pointed out by the experimental analysis, indirect methods for heat accounting can also detect thermal energy consumptions due to the heat conduction from the hot risers of the thermal-hydraulic circuit, when no water flow rate is passing through the radiator. The consideration of such a contribution, as far as HCAs are concerned, has been regarded as an uncertainty source for the resulting heat cost allocation, since it should not be considered as a voluntary individual consumption of thermal energy. Acknowledgments: The authors would like to thank Termoform Srl for providing the set of HCAs for the tests, Carlo Marinari for the effective advice and the useful discussions on the topic of the work and Federico Bari, Riccardo Tisseur and Marco Visione for their contribution to the development and the implementation of the virtual flow sensor EcoThermo. Author Contributions: The work presented in this article is a collaborative development by all of the authors. Conflicts of Interest: The authors declare no conflict of interest. References 1. Buildings—European Commission. Available online: https://ec.europa.eu/energy/en/topics/energy- efficiency/buildings (accessed on 14 January 2017). 2. EN 442-1 Radiators and Convectors—Part 1: Technical Specification and Requirements; European Committee for Standardization: Brussels, Belgium, 2014. 3. EN 442-2 Radiators and Convectors—Part 2: Test Methods and Rating; European Committee for Standardization: Brussels, Belgium, 2014. 4. Marchesi, R.; Tarini, C. Certificazione della potenza di una gamma di corpi scaldanti. Termotecnica 1994, 48, 77–80. 5. Marchesi, R. La camera termostatica di riferimento europeo. Termotecnica 1998, 52, 75–89. 6. EN 834 Heat Cost Allocators for the Determination of the Consumption of Room Heating Radiators. Appliances with Electrical Energy Supply; European Committee for Standardization: Brussels, Belgium, 2013. 7. UNI/TR 11388 Sistemi di Ripartizione Delle Spese di Climatizzazione Invernale Utilizzante Valvole di Corpo Scaldante e Totalizzatore dei Tempi di Inserzione; Ente Nazionale Italiano di Unificazione: Milano, Italy, 2010. 8. The iSERVcmb Project. Available online: http://www.iservcmb.info/ (accessed on 22 February 2017). 9. Enerbrain. Available online: https://www.enerbrain.com/ (accessed on 22 February 2017). 10. Celenza, L.; Dell’Isola, M.; Ficco, G.; Palella, B.I.; Riccio, G. Heat accounting in historical buildings. Energy Build. 2015, 95, 47–56. [CrossRef] 11. Ficco, G.; Celenza, L.; Dell’Isola, M.; Vigo, P. Experimental comparison of heat allocation systems in a residential building at critical conditions. Energy Build. 2016, 130, 477–487. [CrossRef] 12. Arpino, F.; Cortellessa, G.; Dell’Isola, M.; Ficco, G.; Marchesi, R.; Tarini, C. Influence of Installation Conditions on Heating Bodies Thermal Output: Preliminary Experimental Results. Energy Procedia 2016, 101, 74–80. [CrossRef] 13. Marinari, C.; Saba, F.; Grisotto, F.; Orio, M.; Masoero, M. The INRiM thermo-hydraulic mock-up for thermal energy measurement devices: Design, construction and metrological characterization. Energy Procedia 2015, 78, 2304–2309. [CrossRef] 14. Bari, F.; Mereu, D.; Damarco, C.; Greco, C.; Malan, S.; Marchetto, G.; Tirado, S.R.; Tisseur, R.; Violante, M.; Zangari, G.; et al. The EcoThermo project: Key and innovative aspects. Energy Procedia 2015, 78, 2977–2982. [CrossRef] 15. Marinari, C.; Saba, F.; Orio, M. Preliminar Verification of the Functionality and the Accuracy of Heat Metering and Cost Allocation Devices at the INRIM Central Heating System Simulator: The EcoThermo Soft-Sensor Procedure; Technical Report n 9/2015; INRIM: Torino, Italy, 2015. 16. Probert, S.D.; Chester, P.H.; Hobday, R.A. Optimisation of ‘Radiator ’ Shelf Design in Order to Achieve Energy Thrift. Appl. Energy 1989, 32, 71–82. [CrossRef] Buildings 2017, 7, 20 19 of 19 17. IAPWS 2007 Revised Release on the IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam; International Association for the Properties of Water and Steam: Lucerne, Switzerland, 2007. 18. IAPWS Advisory Note No. 1 Uncertainties in Enthalpy for the IAPWS Formulation 1995 for the Thermodynamic Properties of Ordinary Water Substance for General and Scientific Use (IAPWS-95) and the IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam (IAPWS-IF97); International Association for the Properties of Water and Steam: Vejle, Denmark, 2003. 19. Cox, M.G.; Siebert, B.R.L. The use of a Monte Carlo method for evaluating uncertainty and expanded uncertainty. Metrologia 2006, 43, S178–S188. [CrossRef] © 2017 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/). http://www.deepdyve.com/assets/images/DeepDyve-Logo-lg.png Buildings Multidisciplinary Digital Publishing Institute

Experimental Analysis of a Heat Cost Allocation Method for Apartment Buildings

Loading next page...
 
/lp/multidisciplinary-digital-publishing-institute/experimental-analysis-of-a-heat-cost-allocation-method-for-apartment-qurddWiQ4v
Publisher
Multidisciplinary Digital Publishing Institute
Copyright
© 1996-2019 MDPI (Basel, Switzerland) unless otherwise stated
ISSN
2075-5309
DOI
10.3390/buildings7010020
Publisher site
See Article on Publisher Site

Abstract

buildings Article Experimental Analysis of a Heat Cost Allocation Method for Apartment Buildings 1 , 2 , 2 1 1 , 2 Fabio Saba *, Vito Fernicola , Marco Carlo Masoero and Salvatore Abramo Dipartimento Energia, Politecnico di Torino, Corso Duca degli Abruzzi 24, 10129 Torino, Italy; marco.masoero@polito.it (M.C.M.); s220898@studenti.polito.it (S.A.) INRIM, Istituto Nazionale di Ricerca Metrologica, Strada delle Cacce 91, 10135 Torino, Italy; v.fernicola@inrim.it * Correspondence: fabio.saba@polito.it or f.saba@inrim.it; Tel.: +39-011-3919-927 Academic Editor: Cinzia Buratti Received: 23 January 2017; Accepted: 2 March 2017; Published: 6 March 2017 Abstract: The correct estimate of individual thermal energy consumptions, and consequently, a fair heat cost allocation among the residents of apartment buildings with centralized heating systems, represents an important driving force towards energy saving, energy efficiency and the reduction of pollutant emissions. Nowadays, in those contexts where direct heat meters cannot be used because of the layout of the hot water distribution system, electronic Heat Cost Allocators (HCAs) have the highest market share for the assessment of individual thermal energy consumptions. The uncertainty associated with the parameterization of heat cost allocation devices and the installation effects arising in real applications can negatively affect the accuracy of these devices, as far as the estimation of the individual fractions of thermal energy consumption is concerned. This work deals with the experimental analysis of a novel heat cost allocation method for apartment buildings and its comparison with conventional HCAs. The method allows the indirect estimation of the thermal energy exchanged by water radiators without the need for surface temperature measurements, reducing some of the drawbacks associated with the on-site installation. The experimental analysis was carried out in a full-scale central heating system test facility available at the Italian National Metrology Institute (INRIM) and characterized by SI-traceable direct heat meters installed on each water radiator. Keywords: heat accounting; heat cost allocators; individual heat consumption; centralized heating systems; building energy efficiency 1. Introduction Nowadays, buildings are responsible for about 40% of primary energy consumption and 36% of CO emissions in the EU. As about 35% of the EU building stock is over 50 years old, the improvement of the energy efficiency of buildings could lead to a significant reduction of the total EU energy consumption and CO emissions [1]. Space heating in apartment buildings is usually provided by outdated central heating systems, characterized by vertical hydraulic distributions with water radiators connected to the main risers. The refurbishment or the improvement of these types of heating system represents one of the main tasks towards the reduction of CO emissions and can be pursued both by replacing older thermal-hydraulic components and devices and by optimizing their operation and control. The heat cost allocation in apartment buildings, based on the assessment of the actual individual thermal energy consumptions, represents a forceful driver for the residents in order to optimize their household heating management, saving energy and money. Buildings 2017, 7, 20; doi:10.3390/buildings7010020 www.mdpi.com/journal/buildings Buildings 2017, 7, 20 2 of 19 In central heating systems characterized by vertical hydraulic distributions with water radiators of different apartments connected to the same feeding riser, direct heat metering is not feasible for the measurement of individual thermal energy consumptions. Therefore, the indirect estimation of radiator thermal power represents the basis for heat cost allocation, as well as for the design of the heating plant. The European Standard EN 442 [2,3] identifies the measurement model, defines the requirements of the measurement system and describes the procedure to characterize the thermal power exchanged by water radiators. The characteristic coefficients of the radiators, obtained by regression analysis of the experimental data as measured in a thermal chamber [4,5] compliant with the European Standard EN 442, enables an indirect estimate of the steady-state thermal power transferred from the radiator surface to the surrounding environment, once the water mean temperature and the air temperature in proximity of the heating surface are known. In apartment buildings, characterized by a central heating system with vertical feeding risers, the most widespread method for cost allocation of heating consumption makes use of electronic Heat Cost Allocators (HCAs). These devices indirectly estimate the heat consumption of each water radiator by implementing the radiator characteristic coefficients determined according to the EN 442 and by measuring the temperature difference between a specified point on the radiator surface and the surrounding indoor environment. The requirements and the test methods for these kinds of heat cost allocation devices are specified by the European Standard EN 834 [6]. Other heat cost allocation methods, based on the availability of radiator characteristic coefficients, rely on the use of suitable radiator valves for the measurement of the insertion time of each heating body, e.g., according to the Italian standard UNI/TR 11388 [7]. Nowadays, the use of direct or indirect thermal energy measurement devices for the evaluation of individual heating consumptions in apartment buildings, as well as of other sub-metering systems for water, gas and electricity consumptions, is becoming more and more related to the framework of Building Energy Management Systems (BEMS) and the Internet of Things (IoT). Several systems for automatic remote meter readings, centralization and processing of individual heat and water consumptions are commercially available on the market and allow real-time monitoring and management of energy flows. Integrated smart sensor networks provide the necessary measurement data to efficiently manage building energy systems by means of optimization algorithms. Along this line, K2n Ltd., in cooperation with Cardiff University, has produced a powerful cloud-based energy reporting and optimization system, characterized by a different approach to existing meter-based energy monitoring systems, that has been exploited in the framework of the iSERVcmb project to provide the configuration, analysis and optimization of about 2800 HVAC systems throughout Europe [8]. Another example is given by the structure of wireless sensors and actuators and cloud-based algorithms developed by Enerbrain to optimize the operation of HVAC systems, saving energy and improving indoor comfort [9]. The application of the radiator characteristic coefficients when installation and heat transfer conditions significantly differ from the EN 442 reference testing method may lead to significant errors on the estimation of heating consumption. As it is not possible, in real applications, to reproduce the reference installation and heat transfer conditions for water radiators, it is necessary to know the errors and the uncertainty contributions associated with the various heat cost allocation methods, due to the large variety of installation effects [10]. Several in-the-field works were carried out, concerning experimental analyses of heat allocation systems [11,12], focusing on the installation effects on the thermal output of water radiators due to different hydraulic connections, shelves, cavities and obstructions. This work deals with the experimental analysis of an indirect method for the evaluation of individual heat consumptions, carried out at the INRIM central heating system test facility [13]. The proposed method is based on the steady-state indirect estimation of radiator thermal power and exploits the results of the EcoThermo virtual flow sensor [14,15] to estimate the water flow rates Buildings 2017, 7, 20 3 of 19 circulating through each water radiator. Namely, the method allows evaluating the thermal energy exchanged by water radiators by measuring the opening time of radiator valves and by determining the water temperature at radiator outflow from the EcoThermo flow rate estimation, the indoor ambient temperature measurement, the radiator characteristic coefficients and the measurement of main water supply temperature. Although the radiator characteristic coefficients are used for the indirect thermal energy estimation, the proposed method does not rely on temperature measurement at the radiator surface, avoiding some of the drawbacks associated with the on-site installation. A sensitivity analysis of the measurement model of the heat cost allocation method has been carried out, pointing out the potential effects of the uncertainties associated with input quantities on thermal power estimation. As endorsed by the typical flow rate dependence of radiator thermal power and by the results of the sensitivity analysis, the accuracy of the EcoThermo virtual flow sensor, whose typical errors settle within 5%, is adequate for thermal power estimation. For instance, considering a water flow rate equal to 80 L/h, an uncertainty of 5% on flow rate estimation entails a corresponding uncertainty contribution on thermal power estimation of about 0.7%. The results provided by the heat cost allocation method were compared against a reference method, which gives the fractions of heating consumption, as obtained by means of direct heat meters installed on each water radiator. The installation effects associated with water radiators at the INRIM central heating system test facility, which affect the accuracy of any indirect method for thermal power estimation based on radiator characteristic coefficients, are considered by evaluating the deviation between reference direct heat metering and the EN 442 model applied to each water radiator in steady-state conditions. The sharing of thermal energy consumption obtained by the proposed allocation method was observed to be in good agreement (within a maximum deviation of about 10%) with the best indirect estimation of the fractions of heating consumption, which is based on the EN 442 model and takes into account the inherent installation effects that characterize the water radiators at the INRIM test facility. Furthermore, a comparison between the proposed heat cost allocation method and conventional HCAs has been carried out. 2. Thermal Power Exchanged by Water Radiators Whenever possible, the direct measurement of the thermal energy exchanged by a heat-conveying fluid, carried out by means of a flow meter, a pair of temperature sensors and a calculation unit (direct heat meter assembly), is preferable because of its inherent accuracy. However, in many applications, such as heat cost allocation in apartment buildings with vertical distribution pipework, the measurement of flow rate at each water radiator is not feasible both for cost and installation reasons. In these situations, indirect methods for thermal energy measurement, based on the analysis of the heat transfer from the radiator surface or the heat-conveying fluid to the surrounding environment, are often exploited. 2.1. The European Standard EN 442 The European Standard EN 442 [2,3] defines the measurement system and the procedure to characterize the heat emission of water radiators and gives the mathematical model that describes the functional dependence of the radiator thermal power from the temperature difference between water and air in proximity of the heat transfer surface. Such a model represents the basis for any indirect method for the assessment of the thermal energy exchanged by water radiators, since they implement the characteristic coefficients obtained according to the EN 442 standard. The model described by the EN 442 for the assessment of the thermal power exchanged by the heat-conveying fluid flowing through a radiator in steady-state conditions is expressed as follows: Q = K(T T ) (1) m a Buildings 2017, 7, 20 4 of 19 where Q is the thermal power exchanged by the radiator, T is the mean temperature of the fluid between the inlet and outlet sections of the radiator, T is the air temperature at a proper undisturbed distance from the heat transfer surface and K and n are the characteristic coefficients of the radiator. The EN 442 model can also be expressed in the following way: . . T T m a Q = Q (2) N50 where the characteristic coefficient Q is the radiator nominal thermal power, exchanged with N50 (T T ) = 50 C. m a The characteristic coefficients must be determined by regression analysis of experimental data, where measurements of Q and T T are obtained according to a well-defined procedure inside ( ) m a a suitable thermal chamber, compliant with specific requirements defined by the European Standard EN 442. Measurements are carried out in steady-state conditions, such that thermal power can be measured by direct heat metering techniques. The EN 442 defines the test method and specifies the technical requirements of the thermal chamber, fixing the convective and radiative heat transfer conditions between the water radiator under test and the room environment. Thus, the characteristic coefficients of the radiators are associated with a specific operating condition, and their use in real applications to estimate the radiator thermal power may lead to significant errors if the installation and heat transfer conditions of the radiator in the particular environment are sensibly different from the ones inside the thermal chamber. Many factors can significantly affect the accuracy of the thermal power estimation by means of the EN 442 characteristic coefficients; in particular, installation issues, like hydraulic piping connections to the water radiators and their positioning inside cavities or under shelves [12,16], may have a considerable impact on the accuracy of indirect thermal power estimation. Moreover, other influencing factors are worth being noticed, e.g., the painting of radiator surfaces, the huge variety of possible radiant properties of the surrounding bodies and configuration factors that can characterize the installation of the radiator in a particular room, the presence of entrained and dissolved air and the accumulation of impurities, mud or metallic residuals inside the radiator. The possible onset of these factors in real operating conditions determines a variation of the characteristic coefficients of water radiators with respect to those associated with the installation in the thermal chamber as described by the EN 442. 2.2. The INRIM Central Heating System Test Facility A test facility to evaluate the performance of heat cost allocation methods for apartment buildings has been realized at INRIM, the Italian National Metrology Institute, in 2014 [13]. The test facility consists of a full-scale central heating system with 40 water radiators characterized by different shapes, hydraulic connections, dimensions and materials. The thermal-hydraulic network is automatically reconfigurable, in order to reproduce the desired topology of the circuit, and reference direct heat meters are installed on each water radiator to measure the thermal energy exchanged by the heat conveying fluid. Every reference direct heat meter consists of an electromagnetic flow meter, two Pt100 temperature sensors and a thermal energy calculation unit directly implemented on the PC, which receives the converted measurement signals from a Programmable Logic Controller (PLC). The uncertainties associated with the flow rate and temperature measurement chains are listed in Table 1 for a particular heat meter assembly. Buildings 2017, 7, 20 5 of 19 Table 1. Uncertainties of temperature and flow rate measurement chains for a particular heat meter assembly at the INRIM central heating system test facility. Expanded Uncertainty Range (95% conf.int.) Temperature measurement chain from 0 C to 90 C 0.06 C (Pt100 sensor, 4-wire shielded cable, PLC module) Electromagnetic flow meter from 90 L/h to 1800 L/h 0.2% (of the measured value) Buildings 2017, 7, 20 5 of 19 The uncertainty of thermal power measurement, as given by the reference direct heat meters, The uncertainty of thermal power measurement, as given by the reference direct heat meters, results from the propagation of the uncertainties associated with the input quantities through the results from the propagation of the uncertainties associated with the input quantities through the measurement model; it takes into account the stability of measurements at the test facility and the measurement model; it takes into account the stability of measurements at the test facility and the uncertainty related to the equation of state for the estimation of the thermodynamic properties of uncertainty related to the equation of state for the estimation of the thermodynamic properties of water [17,18]. The Monte Carlo method has been used to evaluate the uncertainty associated with water [17,18]. The Monte Carlo method has been used to evaluate the uncertainty associated with thermal power measurements provided by the reference direct heat meters [19]; Figure 1 shows the thermal power measurements provided by the reference direct heat meters [19]; Figure 1 shows the dependence of the relative standard uncertainty of thermal power measurement with respect to the dependence of the relative standard uncertainty of thermal power measurement with respect to the inlet-outlet inlet-outlet w water ater tem temperatur perat eure difd fer ifferenc ence, e, for foa r a particular particular d dir irect he ect heat at met meter er of of ththe e test f test acili facility ty. . Figure 1. Relative standard uncertainty associated with the thermal power measurement of a Figure 1. Relative standard uncertainty associated with the thermal power measurement of a particular particular reference direct heat meter at the INRIM central heating system test facility. reference direct heat meter at the INRIM central heating system test facility. The sub-assemblies of the reference direct heat meters, installed on each water radiator of the The sub-assemblies of the reference direct heat meters, installed on each water radiator of the test test facility, are periodically calibrated in order to ensure the metrological traceability to the facility correspo , are periodically nding reference calibrated standar in ds or . der to ensure the metrological traceability to the corresponding The laboratory allows testing heat cost allocation methods by comparing their results, in terms reference standards. of fractions of thermal energy consumption, with the ones provided by the reference direct heat The laboratory allows testing heat cost allocation methods by comparing their results, in terms of meters. Since the experimental conditions are significantly different from the ones of the thermal fractions of thermal energy consumption, with the ones provided by the reference direct heat meters. chamber, where radiators have been characterized according to the EN 442 standard, it is necessary Since the experimental conditions are significantly different from the ones of the thermal chamber, to evaluate the installation effects on each water radiator at the INRIM test facility, in order to where radiators have been characterized according to the EN 442 standard, it is necessary to evaluate provide significant experimental analyses for any indirect method for heat accounting. Along this the installation effects on each water radiator at the INRIM test facility, in order to provide significant line, the thermal power exchanged by each water radiator of the heating system is estimated in experimental analyses for any indirect method for heat accounting. Along this line, the thermal power steady-state conditions by means of the EN 442 model, using the characteristic coefficients obtained exchanged by each water radiator of the heating system is estimated in steady-state conditions by at the thermal chamber during the radiator characterization, the water temperature measurements at the inlet and outlet flow sections of the radiator and the air temperature measurement at a distance means of the EN 442 model, using the characteristic coefficients obtained at the thermal chamber of 1.5 m from the center of the radiator surface. The resulting relative deviation from the reference during the radiator characterization, the water temperature measurements at the inlet and outlet flow direct measurement of thermal power gives an assessment of the installation effects associated with sections of the radiator and the air temperature measurement at a distance of 1.5 m from the center of the particular water radiator (an example is given in Figure 2). the radiator surface. The resulting relative deviation from the reference direct measurement of thermal The evaluation of the installation effects that characterize the water radiators of the experimental thermal-hydraulic circuit is needed in order to assess the inherent limit of any indirect method for heat cost allocation when tested at the INRIM central heating system facility. Buildings 2017, 7, 20 6 of 19 power gives an assessment of the installation effects associated with the particular water radiator (an example is given in Figure 2). The evaluation of the installation effects that characterize the water radiators of the experimental thermal-hydraulic circuit is needed in order to assess the inherent limit of any indirect method for heat cost allocation when tested at the INRIM central heating system facility. Buildings 2017, 7, 20 6 of 19 (a) (b) Figure 2. Time evolution of: (a) reference thermal power measurement obtained by direct heat Figure 2. Time evolution of: (a) reference thermal power measurement obtained by direct heat metering and indirect thermal power estimation by the EN 442 model for a particular water radiator; metering and indirect thermal power estimation by the EN 442 model for a particular water radiator; (b) corresponding relative deviation between thermal power estimation by the EN 442 model and (b) corresponding relative deviation between thermal power estimation by the EN 442 model and reference direct heat metering. reference direct heat metering. 3. Characterization of the Proposed Heat Cost Allocation Method 3. Characterization of the Proposed Heat Cost Allocation Method A fair heat cost allocation in apartment buildings, where the individual thermal energy A fair heat cost allocation in apartment buildings, where the individual thermal energy consumptions can only be estimated indirectly by means of the semi-empirical relations associated consumptions can only be estimated indirectly by means of the semi-empirical relations associated with each water radiator according to the EN 442 model, is strongly dependent on: with each water radiator according to the EN 442 model, is strongly dependent on:  the correct identification of the thermal characteristics of each water radiator, the correct identification of the thermal characteristics of each water radiator,  the accurate evaluation of the temperature difference between the heat-conveying fluid flowing the accurate evaluation of the temperature difference between the heat-conveying fluid flowing through each radiator and the ambient air in proximity of the radiator surface. through each radiator and the ambient air in proximity of the radiator surface. While the identification of the characteristic coefficients of water radiators represents a common task for the heat cost allocation methods available on the market, the main difference between the While the identification of the characteristic coefficients of water radiators represents a common indirect solutions for the assessment of individual heat consumptions consists of how they estimate task for the heat cost allocation methods available on the market, the main difference between the or approximate the temperature difference between the heat-conveying fluid inside the radiator and indirect solutions for the assessment of individual heat consumptions consists of how they estimate the surrounding air. In particular, HCAs approximate the fluid-air temperature difference with the or approximate the temperature difference between the heat-conveying fluid inside the radiator measurement of the temperature difference between a specified point of the radiator surface and the and the surrounding air. In particular, HCAs approximate the fluid-air temperature difference with surrounding air temperature (close to the radiator surface). Such a temperature difference the measurement of the temperature difference between a specified point of the radiator surface measurement is properly corrected by suitable “coupling coefficients” that depend on the type of and the surrounding air temperature (close to the radiator surface). Such a temperature difference HCA (single sensor or double sensor) and the type of radiator on which the HCA is installed [6]. measurement is properly corrected by suitable “coupling coefficients” that depend on the type of Other heat cost allocation methods, like the ones based on insertion time counters [7], do not use HCA (single sensor or double sensor) and the type of radiator on which the HCA is installed [6]. temperature measurements at the radiator surface, but make proper approximations about the mean Other heat cost allocation methods, like the ones based on insertion time counters [7], do not use water temperature inside the radiators and the indoor air temperatures. temperature measurements at the radiator surface, but make proper approximations about the mean The heat cost allocation method proposed in this work allows assessing the individual fractions water temperature inside the radiators and the indoor air temperatures. of thermal energy consumption by means of:  the measurement of the opening time and opening degree of radiator valves,  the identification of the characteristic coefficients of each water radiator,  the measurements of the indoor air temperature at each living unit where the radiators are installed,  the measurement of the hot water supply temperature at the boiler room, Buildings 2017, 7, 20 7 of 19 The heat cost allocation method proposed in this work allows assessing the individual fractions of thermal energy consumption by means of: the measurement of the opening time and opening degree of radiator valves, the identification of the characteristic coefficients of each water radiator, the measurements of the indoor air temperature at each living unit where the radiators are installed, the measurement of the hot water supply temperature at the boiler room, the estimation of the water flow rate circulating through each water radiator, depending on the opening degree of radiator valves, the total water flow rate flowing through the thermal-hydraulic circuit and the overall hydraulic head loss. The EcoThermo virtual flow sensor provides the estimate of radiator volumetric flow rates, by solving the network model of the thermal-hydraulic circuit, whose branches are preliminarily identified in terms of head loss coefficients. 3.1. Measurement Model The measurement model adopted by the proposed method for the assessment of the thermal power exchanged by each water radiator, in steady-state conditions, can be described as follows: . . Q = Vrc (T T ) < p out in 1/n (3) Vrc T +T p out in = T + 50 (T T ) : a out in N50 In Equation (3), the input quantities of the model are the radiator characteristic coefficients Q N50 and n, the indoor air temperature measurement T near the radiator surface (air temperature measured in the living unit where the radiator is installed), the estimation of radiator water inlet temperature T (approximately equal to the hot water supply temperature at the boiler room) and the estimate of in water volumetric flow rate V passing through the radiator (which depends on the opening degree of the radiator valve). The solution of the measurement model, which is expressed in the form of a non-linear system of Equation (3), gives the estimation of the two unknowns: the thermal power Q and the water outlet temperature T of the radiator. Water density r and specific heat capacity c are functions of out p temperatures T and T and pressure, according to the water equation of state [17]; because of the out in slight pressure dependence of water thermodynamic properties within the thermal-hydraulic operating range of centralized heating systems, water density and specific heat capacity can be evaluated at a rough estimate of the mean absolute water pressure inside the thermal-hydraulic circuit. The thermal energy exchanged by the water radiator is obtained by the time integration of the thermal power during the opening time of the radiator valve. Figure 3 shows the dependence of the thermal power exchanged by a generic water radiator, in steady-state conditions, from the indoor air temperature and the water flow rate, as determined by the model described in Equation (3). The use of the steady-state model also for transient operating conditions, for instance when the radiator surface is warming up, can lead to the overestimation of the thermal power transferred to the surrounding environment, which is balanced out by the heat transfer occurring during the cooling down phase. Buildings 2017, 7, 20 7 of 19  the estimation of the water flow rate circulating through each water radiator, depending on the opening degree of radiator valves, the total water flow rate flowing through the thermal-hydraulic circuit and the overall hydraulic head loss. The EcoThermo virtual flow sensor provides the estimate of radiator volumetric flow rates, by solving the network model of the thermal-hydraulic circuit, whose branches are preliminarily identified in terms of head loss coefficients. 3.1. Measurement Model The measurement model adopted by the proposed method for the assessment of the thermal power exchanged by each water radiator, in steady-state conditions, can be described as follows: ̇ ̇ ( ) 𝑄 = 𝑉 𝜌 𝑐 𝑇 − 𝑇 𝑝 𝑜𝑢𝑡 ̇ (3) 𝑉 𝜌 𝑐 𝑇 + 𝑇 𝑜𝑢𝑡 𝑝 = 𝑇 + 50 [ (𝑇 − 𝑇 )] 𝑎 𝑜𝑢𝑡 2 𝑄 𝑁 50 In Equation (3), the input quantities of the model are the radiator characteristic coefficients 𝑄 and 𝑛 , the indoor air temperature measurement 𝑇 near the radiator surface (air temperature 𝑁 50 𝑎 measured in the living unit where the radiator is installed), the estimation of radiator water inlet temperature 𝑇 (approximately equal to the hot water supply temperature at the boiler room) and the estimate of water volumetric flow rate 𝑉 passing through the radiator (which depends on the opening degree of the radiator valve). The solution of the measurement model, which is expressed in the form of a non-linear system of Equation (3), gives the estimation of the two unknowns: the thermal power 𝑄 and the water outlet temperature 𝑇 of the radiator. Water density 𝜌 and specific heat capacity 𝑐 are functions 𝑜𝑢𝑡 𝑝 of temperatures 𝑇 and 𝑇 and pressure, according to the water equation of state [17]; because of 𝑜𝑢𝑡 the slight pressure dependence of water thermodynamic properties within the thermal-hydraulic operating range of centralized heating systems, water density and specific heat capacity can be evaluated at a rough estimate of the mean absolute water pressure inside the thermal-hydraulic circuit. The thermal energy exchanged by the water radiator is obtained by the time integration of the thermal power during the opening time of the radiator valve. Figure 3 shows the dependence of the thermal power exchanged by a generic water radiator, in steady-state conditions, from the indoor air temperature and the water flow rate, as determined by the model described in Equation Buildings 2017, 7, 20 8 of 19 (3). Figure 3. Dependence of radiator thermal power from indoor air temperature and water flow rate. 3.2. Sensitivity Analysis Measurements and estimations for indoor air temperature, hot water supply temperature, radiator characteristic coefficients and water flow rate circulating through the radiator are essential for the accurate evaluation of the temperature of the fluid at the outlet section of the radiator. Anyway, not the same degree of accuracy is required for the assessment of the mentioned quantities. In order to obtain a ranking of the input quantities of the measurement model in terms of influence on the estimated thermal power exchanged by the water radiator, a sensitivity analysis has been carried out. According to the measurement model described by the system of Equation (3), the output quantity thermal power can be expressed as a function of several input quantities: . . . . Q = Q(T , T , V, Q , n) (4) a in N50 The evaluation of the gradient of Q allows one to get useful information about the impact of each input quantity on thermal power, since the components of the gradient represent the sensitivity coefficients that characterize the allocation model: ( ) . . . . . ¶Q ¶Q ¶Q ¶Q ¶Q rQ = , , , , (5) . . ¶T ¶T ¶n in ¶V ¶Q N50 The gradientrQ has been evaluated numerically by changing one-factor-at-a-time (OFAT) at each point within the multi-dimensional space of the input variables of the model. Moreover, the gradient of the thermal power has been normalized to the thermal power itself, in order to get the relative variation of Q with respect to the unit variation of the input quantities. Table 2 shows the results of the analysis in terms of sensitivity coefficients associated with a specific point within the space of the input variables and an example of evaluation of the uncertainty budget resulting from typical uncertainties assigned to the input quantities. 𝑖𝑛 𝑖𝑛 𝑖𝑛 𝑖𝑛 𝑖𝑛 Buildings 2017, 7, 20 9 of 19 Table 2. Results of the sensitivity analysis and example of uncertainty budget for the proposed heat cost allocation model. Output Relative Input Standard Sensitivity Coefficient Standard Estimate Uncertainty PDF ¶Q 1 Uncertainty x . ¶x . . u(x ) u Q /Q Water inlet 65 C 0.5 C Uniform 2.97 1.48% temperature Indoor ambient 21 C 0.5 C Normal 2.93 1.47% temperature Water flow rate 80 L/h 4 L/h Uniform 0.18 0.72% L/h Radiator nominal thermal power 1400 W 100 W Uniform 0.06 5.95% (at DT = 50 C) Radiator exponent 1.35 (-) 0.1 (-) Uniform 21.54 2.15% (-) Because of the variety of installation and operating conditions for water radiators in real applications, a larger uncertainty has been assigned to the estimations of the radiator characteristic coefficients (higher than 7% for both the radiator nominal thermal power and the radiator exponent). As a consequence of the corresponding sensitivity coefficients, the uncertainty contributions on thermal power are, respectively, around 6% due to the radiator nominal thermal power and 2% due to the radiator exponent. Moreover, as endorsed by the results of the sensitivity analysis, a lower accuracy can be accepted for water flow rate estimation, while particular care should be taken for the evaluation of indoor air temperature and hot water inlet temperature. 3.3. Estimation of Water Flow Rates Circulating through the Radiators In order to estimate the water flow rates circulating through the radiators, the proposed heat cost allocation method uses the results of the soft-sensor EcoThermo, which is applied to the thermal-hydraulic network of the central heating system, where the water radiators are installed. The EcoThermo soft-sensor has been developed and tested in the context of the EU 7thFramework Program for Small and Medium-sized Enterprises FP7-SME-2012 “Innovative green technology for smart energy saving on existing residential buildings with centralized heating/cooling generators” [14]. It is based on the network modelling of the thermal-hydraulic circuit of a generic central heating system, where the hydraulic characteristics (head loss coefficients) of each branch are preliminarily estimated by means of a suitable algorithm for the mathematical identification of the network. The procedure for the mathematical identification of the hydraulic circuit is the core of EcoThermo and consists of the characterization of the minimum number of hydraulic subsystems in which the network can be divided. Namely, the head loss coefficients of each subsystem or closed branch are estimated by non-linear regression of the measurements of water flow rate and corresponding head loss, respectively provided by a fixed volumetric flow meter and two pressure transducers installed at the main supply and return pipe flows in the boiler room. The mathematical relation used to describe the dependence between head loss D p and volumetric flow rate V in a generic branch of the hydraulic network can be expressed as follows: D p = aV (6) where a and b are the characteristic hydraulic coefficients of the branch. The use of a suitable pump equipped with an inverter or other flow rate control systems is necessary in order to generate a representative set of water flow rates and head losses for the hydraulic characterization of the branches. Buildings 2017, 7, 20 10 of 19 Once the hydraulic circuit has been identified, the water volumetric flow rates circulating through each open radiator can be estimated from the overall volumetric flow rate and head loss measurements at the main pipe flow, by solving the network model. The EcoThermo soft-sensor has been validated at the INRIM central heating system test facility, in a wide set of network topologies and operating conditions [14,15]. Figure 4 shows an example of the results obtained by EcoThermo for the estimation of the water flow rate through a particular radiator of the thermal-hydraulic circuit. Buildings 2017, 7, 20 10 of 19 (a) (b) Figure 4. Time evolution of: (a) EcoThermo flow rate estimation and reference water flow rate Figure 4. Time evolution of: (a) EcoThermo flow rate estimation and reference water flow rate measurement at a particular radiator; (b) corresponding relative error of EcoThermo estimation with measurement at a particular radiator; (b) corresponding relative error of EcoThermo estimation with respect to reference water flow rate measurement. respect to reference water flow rate measurement. The soft-sensor EcoThermo could also be used as an effective tool for the optimal management The soft-sensor EcoThermo could also be used as an effective tool for the optimal management of of central heating systems; for instance, it could enable the dynamic balancing of the hydraulic central heating systems; for instance, it could enable the dynamic balancing of the hydraulic circuit, circuit, preventing either too high or too low flow rates at each water radiator. Moreover, it could preventing either too high or too low flow rates at each water radiator. Moreover, it could ensure that ensure that radiator valves operate with a stable and predictable hydraulic response, in terms of radiator valves operate with a stable and predictable hydraulic response, in terms of fixed dependence fixed dependence between water flow rate and opening degree. between water flow rate and opening degree. 4. Results of the Experimental Analysis 4. Results of the Experimental Analysis The proposed heat cost allocation method has been tested at the INRIM central heating system The proposed heat cost allocation method has been tested at the INRIM central heating system test facility, where each water radiator is equipped with a reference direct heat meter for thermal test facility, where each water radiator is equipped with a reference direct heat meter for thermal energy measurement. A set of 11 water radiators, which consists of 7 aluminum, 2 cast iron and energy measurement. A set of 11 water radiators, which consists of 7 aluminum, 2 cast iron and 2 tubular steel radiators distributed on four different risers, as shown in Figure 5, has been selected 2 tubular steel radiators distributed on four different risers, as shown in Figure 5, has been selected for for the tests. the tests. Buildings 2017, 7, 20 11 of 19 Buildings 2017, 7, 20 11 of 19 Figure 5. Scheme of the thermal-hydraulic circuit of the INRIM test facility and selected set of Figure 5. Scheme of the thermal-hydraulic circuit of the INRIM test facility and selected set of waterwater rad radiators. iators. The pump and the heater have been programmed to feed the 11 radiators of the The pump and the heater have been programmed to feed the 11 radiators of the thermal-hydraulic thermal-hydraulic circuit with the desired water flow rate and temperature, and the motorized circuit with the desired water flow rate and temperature, and the motorized radiator valves have been radiator valves have been automatically controlled to set the desired opening/closing times. The task automatically controlled to set the desired opening/closing times. The task for the heat cost allocation for the heat cost allocation method is to provide the individual fractions of thermal energy method is to provide the individual fractions of thermal energy consumption for each water radiator, consumption for each water radiator, defined as: defined as: 𝑓 = 𝑖 (7) f = (7) 11 𝑗 𝑗 =1 j=1 where 𝑄 is the thermal energy exchanged by the i-th water radiator, calculated by the time where Q is the thermal energy exchanged by the i-th water radiator, calculated by the time integration integration of the thermal power estimated by means of the model described by the system of of the thermal power estimated by means of the model described by the system of Equation (3). Equation (3). The characteristic thermal coefficients of water radiators, which are used by the The characteristic thermal coefficients of water radiators, which are used by the allocation method to allocation method to estimate the individual thermal energy consumptions, are obtained from the estimate the individual thermal energy consumptions, are obtained from the radiator datasheets and radiator datasheets and are listed in Table 3. are listed in Table 3. Table 3. Characteristic coefficients of water radiators. Nominal Thermal Exponent Power at DT = 50 C Q (W) N50 Aluminum radiators 1467 1.359 Cast iron radiators 1427 1.3679 Tubular steel radiators 1482 1.28 The proposed method has been tested by evaluating, for each water radiator, the deviation between the estimated fraction of thermal energy consumption and the one measured by the reference direct heat meters. The relative deviations from the reference measurements of the individual fractions of heat consumption ( f ) can be expressed as follows: i,REF f f i i,REF # = (8) i,REF Moreover, the heat cost allocation method has been compared against conventional HCAs installed on the set of selected radiators (Figure 6), based on the relative deviations from the reference fractions of heat consumption provided by direct heat meters. HCAs have been programmed using the radiator Buildings 2017, 7, 20 12 of 19 Table 3. Characteristic coefficients of water radiators. Nominal Thermal Exponent Power at ΔT = 50 °C 𝑸 (W) 𝑵𝟓𝟎 Aluminum radiators 1467 1.359 Cast iron radiators 1427 1.3679 Tubular steel radiators 1482 1.28 The proposed method has been tested by evaluating, for each water radiator, the deviation between the estimated fraction of thermal energy consumption and the one measured by the reference direct heat meters. The relative deviations from the reference measurements of the individual fractions of heat consumption (𝑓 ) can be expressed as follows: 𝑖 ,𝑅𝐸𝐹 𝑓 − 𝑓 𝑖 𝑖 ,𝑅𝐸𝐹 𝜀 = (8) 𝑖 ,𝑅𝐸𝐹 Buildings 2017, 7, 20 12 of 19 Moreover, the heat cost allocation method has been compared against conventional HCAs installed on the set of selected radiators (Figure 6), based on the relative deviations from the reference fractions of heat consumption provided by direct heat meters. HCAs have been characteristic coefficients listed in Table 3 and the rating factors for the device-radiator coupling programmed using the radiator characteristic coefficients listed in Table 3 and the rating factors for provided by the manufacturer, according to the EN 834 standard [6]. the device-radiator coupling provided by the manufacturer, according to the EN 834 standard [6]. Figure 6. Experimental setup at the INRIM central heating system test facility. Figure 6. Experimental setup at the INRIM central heating system test facility. The indoor air temperature measurements, which are needed by the proposed heat cost allocation method to estimate the fractions of thermal energy consumption, are provided by five The indoor air temperature measurements, which are needed by the proposed heat cost allocation Pt100 temperature sensors placed at different heights, corresponding to the position of water method to estimate the fractions of thermal energy consumption, are provided by five Pt100 radiators on the risers, at about 1.5 m from the nearest heating surfaces (Figure 6). temperature sensors placed at different heights, corresponding to the position of water radiators Furthermore, the indoor air temperature measurements are used to evaluate the individual on the risers, at about 1.5 m from the nearest heating surfaces (Figure 6). fractions of thermal energy consumption by means of the EN 442 model. Such a model, in addition Furthermore, the indoor air temperature measurements are used to evaluate the individual to the indoor air temperature measurements and the characteristic thermal coefficients of each fractions of thermal energy consumption by means of the EN 442 model. Such a model, in addition to radiator, uses the reference temperature sensors directly immersed at the inlet and outlet flow the indoor air temperature measurements and the characteristic thermal coefficients of each radiator, sections of each water radiator to evaluate the water mean temperatures. As discussed in Section 2.2, uses the reference temperature sensors directly immersed at the inlet and outlet flow sections of each the comparison between the indirect estimation of radiator thermal power by means of the EN 442 water mo radiator del and to the evaluate reference the direct water meas mean uremen temperatur t of the thermal es. As po discussed wer exchange in Section d by the 2.2 heat , the -conv compari eying son fluid passing through the radiator in steady-state conditions allows one to evaluate the uncertainty between the indirect estimation of radiator thermal power by means of the EN 442 model and the reference direct measurement of the thermal power exchanged by the heat-conveying fluid passing through the radiator in steady-state conditions allows one to evaluate the uncertainty contribution due to the particular installation and operating conditions in the laboratory during the tests. As well as in real applications, the installation and operating conditions at the INRIM central heating system may be significantly different from the ones to which the characteristic thermal coefficients of the radiators refer. For this reason, the performance of any heat cost allocation method based on the EN 442 model must take into account the inherent limit due to the particular installation and operating conditions at the test facility, which is highlighted by the deviation between the individual heat consumptions provided by the EN 442 model and the reference direct heat metering in steady-state conditions. A Pt100 temperature sensor directly immersed in the main hot water supply flow exiting from the heater gives the estimation of radiator inlet temperatures, which are needed by the heat cost allocation method to evaluate the fractions of thermal energy consumption. Such an approximation is justified, in real applications, by the economic and practical constraints related to the installation of thermometers at the inlet sections of each water radiator of the central heating system. The experiments for testing the proposed heat cost allocation method are characterized by the following operating conditions: Balanced hydraulic network: the thermal-hydraulic circuit of the central heating system has been preliminarily balanced, as should be recommended in real applications, in order to obtain a uniform flow rate distribution among the water radiators; Buildings 2017, 7, 20 13 of 19 contribution due to the particular installation and operating conditions in the laboratory during the tests. As well as in real applications, the installation and operating conditions at the INRIM central heating system may be significantly different from the ones to which the characteristic thermal coefficients of the radiators refer. For this reason, the performance of any heat cost allocation method based on the EN 442 model must take into account the inherent limit due to the particular installation and operating conditions at the test facility, which is highlighted by the deviation between the individual heat consumptions provided by the EN 442 model and the reference direct heat metering in steady-state conditions. A Pt100 temperature sensor directly immersed in the main hot water supply flow exiting from the heater gives the estimation of radiator inlet temperatures, which are needed by the heat cost allocation method to evaluate the fractions of thermal energy consumption. Such an approximation is justified, in real applications, by the economic and practical constraints related to the installation of thermometers at the inlet sections of each water radiator of the central heating system. The experiments for testing the proposed heat cost allocation method are characterized by the following operating conditions: Buildings 2017, 7, 20 13 of 19  Balanced hydraulic network: the thermal-hydraulic circuit of the central heating system has been preliminarily balanced, as should be recommended in real applications, in order to obtain Automatic control of the opening/closing time of radiator valves: the motorized supply valves a uniform flow rate distribution among the water radiators; of the 11 water radiators, which can only set on their fully-open/closed state, are preliminarily  Automatic control of the opening/closing time of radiator valves: the motorized supply valves programmed in terms of opening/closing times, simulating typical daily occupancy behaviors, of the 11 water radiators, which can only set on their fully-open/closed state, are preliminarily as shown in Figure 7; programmed in terms of opening/closing times, simulating typical daily occupancy behaviors, Constant as shown water in Figur supply e 7; temperature and constant pump speed: the heater is set to ensure  Constant water supply temperature and constant pump speed: the heater is set to ensure a a constant hot water supply temperature of 65 C, and the pump is set to operate at 45% of constant hot water supply temperature of 65 °C, and the pump is set to operate at 45% of its its maximum speed; maximum speed; Cooling down of radiator surfaces: the tests include the time needed for the complete natural  Cooling down of radiator surfaces: the tests include the time needed for the complete natural cooling down of the heat transfer surface of radiators after either the closing of radiator valves or cooling down of the heat transfer surface of radiators after either the closing of radiator valves the shutdown of the heater; this is necessary in order to compare the heat cost allocation obtained or the shutdown of the heater; this is necessary in order to compare the heat cost allocation by means of HCAs and the EN 442 model, with the one provided by reference direct heat meters; obtained by means of HCAs and the EN 442 model, with the one provided by reference direct Long heat met time duration ers; of the tests: the tests are characterized by long-time recording, such that the  Long time duration of the tests: the tests are characterized by long-time recording, such that the resolution error of the 11 HCAs becomes negligible if compared to the corresponding amount of resolution error of the 11 HCAs becomes negligible if compared to the corresponding amount totalized units of heating consumption. of totalized units of heating consumption. Figure 7. Programmed daily opening time of radiator valves. Figure 7. Programmed daily opening time of radiator valves. In such an experimental test condition, the estimations of the fractions of heating consumption associated with each water radiator, as given by the proposed heat cost allocation method, have been compared to the ones provided by the reference direct heat meters. In order to take into account the installation effects that characterize the particular operation of water radiators at the INRIM test facility, the individual fractions of thermal energy consumption have been evaluated also by means of the EN 442 model. It is worth noticing how the operating conditions designed for the test may deviate from what usually happens in real applications. For instance, balanced hydraulic networks, although recommended, are not so typical for old buildings, while the control of supply temperature, pump speed and radiator valves may be affected by hysteresis and communication issues or can be designed with different criteria, e.g., supply temperature and flow can be controlled by external ambient temperature measurement. Moreover, the ON-OFF operation of water radiators, as programmed for the test, is getting more and more unusual in current applications, because of the growing use of thermostatic radiator valves, which allows modulating the radiator thermal power according to the desired indoor air temperature. Figure 8 shows the time trend of the indoor air temperature measurements during the test, as given by the five Pt100 thermometers installed at different heights inside the laboratory in proximity of the heating surfaces of the radiators. The time evolution follows the programmed opening/closing times Buildings 2017, 7, 20 14 of 19 In such an experimental test condition, the estimations of the fractions of heating consumption associated with each water radiator, as given by the proposed heat cost allocation method, have been compared to the ones provided by the reference direct heat meters. In order to take into account the installation effects that characterize the particular operation of water radiators at the INRIM test facility, the individual fractions of thermal energy consumption have been evaluated also by means of the EN 442 model. It is worth noticing how the operating conditions designed for the test may deviate from what usually happens in real applications. For instance, balanced hydraulic networks, although recommended, are not so typical for old buildings, while the control of supply temperature, pump speed and radiator valves may be affected by hysteresis and communication issues or can be designed with different criteria, e.g., supply temperature and flow can be controlled by external ambient temperature measurement. Moreover, the ON-OFF operation of water radiators, as programmed for the test, is getting more and more unusual in current applications, because of the growing use of thermostatic radiator valves, which allows modulating the radiator thermal power according to the desired indoor air temperature. Figure 8 shows the time trend of the indoor air temperature measurements during the test, as given by the five Pt100 thermometers installed at different heights inside the laboratory in proximity of the heating surfaces of the radiators. The time evolution follows the programmed opening/closing Buildings 2017, 7, 20 14 of 19 times of water radiators and highlights the vertical stratification of air temperatures inside the laboratory. Indoor air temperature has been observed ranging from about 18 °C (at a 1-m height of water radiators and highlights the vertical stratification of air temperatures inside the laboratory. from the floor) to a maximum of about 25 °C (at a 3-m height from the floor). Although the air temperature measurement points are equally spaced on the height of the laboratory, a slightly Indoor air temperature has been observed ranging from about 18 C (at a 1-m height from the floor) to stronger thermal stratification was observed between the second and third floors, with respect to the a maximum of about 25 C (at a 3-m height from the floor). Although the air temperature measurement first and points are equally spaced on the height of the laboratory, a slightly stronger thermal stratification was second ones. observed between the second and third floors, with respect to the first and second ones. Figure 8. Time evolution of indoor air temperature measurements during the test. Figure 8. Time evolution of indoor air temperature measurements during the test. Figure 9 shows the results of the test in terms of fractions of thermal energy consumption, as Figure 9 shows the results of the test in terms of fractions of thermal energy consumption, as given given by the reference direct heat meters, the EN 442 model applied to each water radiator, the by the reference direct heat meters, the EN 442 model applied to each water radiator, the HCAs and HCAs and the proposed heat cost allocation method. The last, as described in Section 3.3, exploits the proposed heat cost allocation method. The last, as described in Section 3.3, exploits the results of the results of the EcoThermo soft-sensor to estimate the water flow rates circulating through each Buildings 2017, 7, 20 15 of 19 the EcoThermo water radiato soft-sensor r. to estimate the water flow rates circulating through each water radiator. Figure 9. Fractions of heating consumption associated with water radiators. HCA, Heat Cost Allocator. Figure 9. Fractions of heating consumption associated with water radiators. HCA, Heat Cost Allocator. All of the heat cost allocation methods, as well as reference direct heat metering, provide greater All of the heat cost allocation methods, as well as reference direct heat metering, provide fractions of heat consumption for second floor radiators (N13, N14, N15, S11), which are open for greater fractions of heat consumption for second floor radiators (N13, N14, N15, S11), which are a longer time (16 h/day). Focusing on radiators N20 and N10 (same material, shape and dimension), open for a longer time (16 h/day). Focusing on radiators N20 and N10 (same material, shape and which are installed on the same riser at the first and third floors, respectively, and are characterized by dimension), which are installed on the same riser at the first and third floors, respectively, and are almost the same feeding flow rate and the same opening time (8 h/day), it can be observed that the characterized by almost the same feeding flow rate and the same opening time (8 h/day), it can be reference fractions of heat consumption are lower for radiator N10 than for N20 (about 6% for radiator observed that the reference fractions of heat consumption are lower for radiator N10 than for N20 N10 (a and bout 7% 6% for forN20), radiator mainly N10 and because 7% for of N20) indoor , mainly b air temperatur ecause of inde oor stratification. air temperature The strsame atification. behavior The same behavior cannot be observed for the heat cost allocation provided by indirect methods, cannot be observed for the heat cost allocation provided by indirect methods, like the EN 442 model like the EN 442 model and HCAs, since their estimates are significantly affected by installation effects, and the fractions of heating consumptions are strongly correlated. The proposed heat cost allocation method is sensitive to installation effects, as well, but the evaluation of the heat output only when the radiator valve is open could slightly improve or decrease the accuracy of the estimated fractions of heat consumption, depending on the frequency of the ON-OFF operation of radiator valves and on the uniformity of installation effects. Moreover, while the accuracy of radiator characteristic coefficients is ensured for describing the heat transfer occurring when water is flowing through the radiator, their use for the estimation of the thermal power transferred from the hot surface to the surrounding air when the radiator valve is closed may lead to errors that cannot be related, exclusively, to installation effects. The relative deviations between the individual fractions of heating consumption and the reference ones have been evaluated for the EN 442 model, the HCAs and the proposed allocation method, and the results are shown in Figure 10. The sharing of thermal energy consumption provided by the proposed allocation method reproduces quite accurately the heat cost allocation obtained by means of the EN 442 model, with slight differences due to the evaluation of radiator thermal power only during the opening time of the corresponding valves and to the assumptions made for estimating the water inlet temperatures and flow rates at each radiator. Such deviations between the proposed heat cost allocation method and the EN 442 model settle within 10% and are greater for third floor radiators (N10, N9, N8 and S6), because of the more frequent ON-OFF operation for such heat delivery points. The contribution of the inherent installation effects that characterize the radiators at the central heating system test facility is such that the relative deviations of the EN 442 model, with respect to the reference fractions of heating consumption, vary within ±10% for most of the radiators, except for radiators N18 and N19, characterized by relative deviations of about −15% and −13%, respectively. As far as the proposed heat cost allocation method is concerned, the modulus of the maximum relative deviation from the reference fraction of heat consumption Buildings 2017, 7, 20 15 of 19 and HCAs, since their estimates are significantly affected by installation effects, and the fractions of heating consumptions are strongly correlated. The proposed heat cost allocation method is sensitive to installation effects, as well, but the evaluation of the heat output only when the radiator valve is open could slightly improve or decrease the accuracy of the estimated fractions of heat consumption, depending on the frequency of the ON-OFF operation of radiator valves and on the uniformity of installation effects. Moreover, while the accuracy of radiator characteristic coefficients is ensured for describing the heat transfer occurring when water is flowing through the radiator, their use for the estimation of the thermal power transferred from the hot surface to the surrounding air when the radiator valve is closed may lead to errors that cannot be related, exclusively, to installation effects. The relative deviations between the individual fractions of heating consumption and the reference ones have been evaluated for the EN 442 model, the HCAs and the proposed allocation method, and the results are shown in Figure 10. The sharing of thermal energy consumption provided by the proposed allocation method reproduces quite accurately the heat cost allocation obtained by means of the EN 442 model, with slight differences due to the evaluation of radiator thermal power only during the opening time of the corresponding valves and to the assumptions made for estimating the water inlet temperatures and flow rates at each radiator. Such deviations between the proposed heat cost allocation method and the EN 442 model settle within 10% and are greater for third floor radiators (N10, N9, N8 and S6), because of the more frequent ON-OFF operation for such heat delivery points. The contribution of the inherent installation effects that characterize the radiators at the central heating system test facility is such that the relative deviations of the EN 442 model, with respect to the reference fractions of heating consumption, vary within 10% for most of the radiators, except for Buildings 2017, 7, 20 16 of 19 radiators N18 and N19, characterized by relative deviations of about 15% and 13%, respectively. does not As far as the proposed heat cost allocation method is concerned, the modulus of the maximum relative exceed 11%. deviation from the reference fraction of heat consumption does not exceed 11%. Figure 10. Relative deviations from reference measurements of individual fractions of Figure 10. Relative deviations from reference measurements of individual fractions of heating consumption. heating consumption. On the other hand, the heat cost allocation obtained by means of HCAs describes a scenario On the other hand, the heat cost allocation obtained by means of HCAs describes a scenario of of individual fractions of thermal energy consumption that is very different from the actual one, individual fractions of thermal energy consumption that is very different from the actual one, with with relative deviations with respect to reference heat cost allocation up to about 30%. This may be due relative deviations with respect to reference heat cost allocation up to about 30%. This may be due to to the thdif e different ferent types types of of mounting mounting adopt adopted ed for forth the e inst installation allation of of HCA HCAs s on th on e the diffe dif rent fer typ ent es types of water of water radiators used for the test. In fact, while the same type of installation is more likely to result in the radiators used for the test. In fact, while the same type of installation is more likely to result in the same accuracy on the estimation of individual heat consumptions, the different mountings of HCAs same accuracy on the estimation of individual heat consumptions, the different mountings of HCAs in in the same heating system may entail large errors in terms of fractions of thermal energy the same heating system may entail large errors in terms of fractions of thermal energy consumption. consumption. In order to evaluate this effect, the heat cost allocation has been carried out In order to evaluate this effect, the heat cost allocation has been carried out considering only the seven considering only the seven aluminum radiators of the selected set, characterized by the same mounting installation of the HCA on the radiator surface. The results in terms of relative deviations from the reference fractions of thermal energy consumption are shown in Figure 11. Buildings 2017, 7, 20 16 of 19 does not exceed 11%. Figure 10. Relative deviations from reference measurements of individual fractions of heating consumption. On the other hand, the heat cost allocation obtained by means of HCAs describes a scenario of individual fractions of thermal energy consumption that is very different from the actual one, with relative deviations with respect to reference heat cost allocation up to about 30%. This may be due to the different types of mounting adopted for the installation of HCAs on the different types of water radiators used for the test. In fact, while the same type of installation is more likely to result in the same accuracy on the estimation of individual heat consumptions, the different mountings of HCAs Buildings 2017, 7, 20 16 of 19 in the same heating system may entail large errors in terms of fractions of thermal energy consumption. In order to evaluate this effect, the heat cost allocation has been carried out considering only the seven aluminum radiators of the selected set, characterized by the same aluminum radiators of the selected set, characterized by the same mounting installation of the HCA on mounting installation of the HCA on the radiator surface. The results in terms of relative deviations the radiator surface. The results in terms of relative deviations from the reference fractions of thermal from the reference fractions of thermal energy consumption are shown in Figure 11. energy consumption are shown in Figure 11. Figure 11. Relative deviations from reference measurements of individual fractions of heating consumption, only for the aluminum radiators (cast iron and steel radiators have been excluded for the assessment of heat cost allocation). A significant reduction of the relative deviations in particular for HCAs at radiators N10, N9, N8 and S6 can be observed. This is due to the uniformity of the types of mounting installation and to the correlation between the fractions of heating consumption. The maximum relative deviation with respect to the reference heat cost allocation obtained by direct heat meters is about 15% for HCAs (radiator N10), while, as far as the proposed allocation method is concerned, the relative deviations settle within 6% for all seven aluminum radiators. Moreover, it is worth noticing that HCAs and the EN 442 model, unlike both the reference direct heat meters and the proposed heat cost allocation method, are able to detect the heat transfer from the radiator surface, even when the water flow rate is not circulating through the radiator. This may happen either when the radiator valve closes and the stagnant hot water remains inside the radiator tubes or when a closed radiator is connected to a riser in which hot water is circulating because of the presence of at least one open radiator; in such a case, depending on the piping connections of the hydraulic circuit and the position of the closed radiator with respect to the open ones, heat is transferred by conduction from the hot riser to the closed radiator (through the pipe wall and the stagnant water). While the additional heat transfer, which occurs because of the presence of stagnant hot water inside a closed radiator, is balanced out by the smaller thermal power transferred to the surrounding air during the warming up of the radiator surface, the heat conduction from the risers behaves as an offset. In order to compare the fractions of heating consumption provided by the EN 442 model with the ones obtained by both the reference direct heat meters and the proposed allocation method, the heat cost allocation evaluated by the EN 442 model has been carried out excluding the contribution due to heat conduction from the risers when the water flow rate is not circulating through the radiators. Such a correction is taken into account since the contribution due to the heat conduction from the hot risers, when the radiator valve is closed, should not be considered as a voluntary individual thermal energy consumption. As far as the heat cost allocation provided by HCAs is concerned, the heat conduction contribution should be taken into account within the uncertainty budget associated with the estimated fractions of heating consumption, since it is not possible to correct the readings of Buildings 2017, 7, 20 17 of 19 each HCA, by separating the heat conduction contribution from the total amount of units of thermal energy consumption. 5. Conclusions The method described in this work, for heat accounting in apartment buildings, has provided good results in terms of accuracy on the estimation of individual fractions of thermal energy consumptions, as pointed out by the preliminary experimental analysis carried out at the INRIM central heating system test facility. The sharing of heat consumption evaluated by the proposed method has been observed to be very close to the heat cost allocation provided by the EN 442 model (within a maximum deviation of about 10%), which has been calculated using the characteristic radiator coefficients, the reference inlet and outlet water temperature measurements for each radiator and the air temperature measurements in proximity of the heat transfer surfaces. The contribution of the installation effects that characterize the radiators at the INRIM central heating system test facility is such that the relative deviations between the fractions of heat consumption provided by the EN 442 model and the reference ones given by direct heat meters vary within 10% for most of the radiators, except for two radiators of the set, characterized by relative deviations of about 15% and 13%. The results of the test show that the proposed method is mainly affected by the inherent installation effects that characterize the test facility, endorsing the effectiveness of the measurement model for the estimation of individual thermal energy consumptions. The approach adopted by the proposed heat cost allocation method, consisting of the evaluation of thermal power only when the radiator valve is open, could slightly improve or decrease the accuracy of the estimated fractions of heat consumption, depending on the frequency of the ON-OFF operation of radiator valves and on the uniformity of installation effects. Moreover, it could avoid possible errors that may result from the application of radiator characteristic coefficients to the evaluation of the exchanged thermal power when water is not flowing through the radiator. The assumptions made for the approximation of water inlet temperatures of radiators and the use of the EcoThermo soft-sensor for the estimation of radiator flow rates do not entail a significant reduction of the accuracy of the heat cost allocation method, as predicted by the sensitivity analysis. The modulus of the maximum relative deviation from the reference fraction of heating consumption does not exceed 11%. The proposed method has been compared also with conventional HCAs, and the results of the test have pointed out the importance of ensuring homogeneous mounting installations of these devices on the set of water radiators selected for the test. Namely, the different mounting adopted for tubular steel radiators, with respect to aluminum and cast iron radiators, has led to significant deviations from reference fractions of heat consumption, even up to 30%. In order to verify the effect of the mounting installation on the accuracy of HCAs, the heat cost allocation has been carried out considering only the seven aluminum radiators of the selected set, characterized by the same mounting of HCAs on radiator surfaces. A significant reduction of the relative deviations with respect to the reference fractions of heating consumptions has been observed; namely, a maximum deviation of about 15% has been obtained for HCAs, while, regarding the proposed allocation method, the relative deviations settled within 6% for all seven aluminum radiators. As far as the in-the-field application is concerned, the proposed indirect method for heat accounting is safe from some of the installation effects that may affect the accuracy of HCAs, like the on-site mounting of the devices and the identification of the radiator-device coupling coefficients, since it does not rely on the temperature measurement of the radiator external surface. Moreover, in order to ensure the correct application of the heat cost allocation model and the effective use of the EcoThermo soft-sensor, the signals related to the state (opening degree) and opening time of radiator valves, indoor air temperatures, hot water supply temperature, total flow rate and overall head loss, must be transmitted to a suitable data acquisition system and logged at a proper sampling time. Furthermore, it is worth observing that the deviations between the fractions of heating consumption obtained by indirect heat cost allocation methods and the reference ones provided Buildings 2017, 7, 20 18 of 19 by direct heat meters can also be influenced by the capability of indirect methods to assess the radiator heat transfer even if no water is circulating. For such a reason, the tests have been carried out either by comparing direct and indirect methods in steady-state operating conditions only or by considering test durations that ensure the indirect estimation of radiator thermal power to balance out the symmetric warming up and cooling down transients. Moreover, as pointed out by the experimental analysis, indirect methods for heat accounting can also detect thermal energy consumptions due to the heat conduction from the hot risers of the thermal-hydraulic circuit, when no water flow rate is passing through the radiator. The consideration of such a contribution, as far as HCAs are concerned, has been regarded as an uncertainty source for the resulting heat cost allocation, since it should not be considered as a voluntary individual consumption of thermal energy. Acknowledgments: The authors would like to thank Termoform Srl for providing the set of HCAs for the tests, Carlo Marinari for the effective advice and the useful discussions on the topic of the work and Federico Bari, Riccardo Tisseur and Marco Visione for their contribution to the development and the implementation of the virtual flow sensor EcoThermo. Author Contributions: The work presented in this article is a collaborative development by all of the authors. Conflicts of Interest: The authors declare no conflict of interest. References 1. Buildings—European Commission. Available online: https://ec.europa.eu/energy/en/topics/energy- efficiency/buildings (accessed on 14 January 2017). 2. EN 442-1 Radiators and Convectors—Part 1: Technical Specification and Requirements; European Committee for Standardization: Brussels, Belgium, 2014. 3. EN 442-2 Radiators and Convectors—Part 2: Test Methods and Rating; European Committee for Standardization: Brussels, Belgium, 2014. 4. Marchesi, R.; Tarini, C. Certificazione della potenza di una gamma di corpi scaldanti. Termotecnica 1994, 48, 77–80. 5. Marchesi, R. La camera termostatica di riferimento europeo. Termotecnica 1998, 52, 75–89. 6. EN 834 Heat Cost Allocators for the Determination of the Consumption of Room Heating Radiators. Appliances with Electrical Energy Supply; European Committee for Standardization: Brussels, Belgium, 2013. 7. UNI/TR 11388 Sistemi di Ripartizione Delle Spese di Climatizzazione Invernale Utilizzante Valvole di Corpo Scaldante e Totalizzatore dei Tempi di Inserzione; Ente Nazionale Italiano di Unificazione: Milano, Italy, 2010. 8. The iSERVcmb Project. Available online: http://www.iservcmb.info/ (accessed on 22 February 2017). 9. Enerbrain. Available online: https://www.enerbrain.com/ (accessed on 22 February 2017). 10. Celenza, L.; Dell’Isola, M.; Ficco, G.; Palella, B.I.; Riccio, G. Heat accounting in historical buildings. Energy Build. 2015, 95, 47–56. [CrossRef] 11. Ficco, G.; Celenza, L.; Dell’Isola, M.; Vigo, P. Experimental comparison of heat allocation systems in a residential building at critical conditions. Energy Build. 2016, 130, 477–487. [CrossRef] 12. Arpino, F.; Cortellessa, G.; Dell’Isola, M.; Ficco, G.; Marchesi, R.; Tarini, C. Influence of Installation Conditions on Heating Bodies Thermal Output: Preliminary Experimental Results. Energy Procedia 2016, 101, 74–80. [CrossRef] 13. Marinari, C.; Saba, F.; Grisotto, F.; Orio, M.; Masoero, M. The INRiM thermo-hydraulic mock-up for thermal energy measurement devices: Design, construction and metrological characterization. Energy Procedia 2015, 78, 2304–2309. [CrossRef] 14. Bari, F.; Mereu, D.; Damarco, C.; Greco, C.; Malan, S.; Marchetto, G.; Tirado, S.R.; Tisseur, R.; Violante, M.; Zangari, G.; et al. The EcoThermo project: Key and innovative aspects. Energy Procedia 2015, 78, 2977–2982. [CrossRef] 15. Marinari, C.; Saba, F.; Orio, M. Preliminar Verification of the Functionality and the Accuracy of Heat Metering and Cost Allocation Devices at the INRIM Central Heating System Simulator: The EcoThermo Soft-Sensor Procedure; Technical Report n 9/2015; INRIM: Torino, Italy, 2015. 16. Probert, S.D.; Chester, P.H.; Hobday, R.A. Optimisation of ‘Radiator ’ Shelf Design in Order to Achieve Energy Thrift. Appl. Energy 1989, 32, 71–82. [CrossRef] Buildings 2017, 7, 20 19 of 19 17. IAPWS 2007 Revised Release on the IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam; International Association for the Properties of Water and Steam: Lucerne, Switzerland, 2007. 18. IAPWS Advisory Note No. 1 Uncertainties in Enthalpy for the IAPWS Formulation 1995 for the Thermodynamic Properties of Ordinary Water Substance for General and Scientific Use (IAPWS-95) and the IAPWS Industrial Formulation 1997 for the Thermodynamic Properties of Water and Steam (IAPWS-IF97); International Association for the Properties of Water and Steam: Vejle, Denmark, 2003. 19. Cox, M.G.; Siebert, B.R.L. The use of a Monte Carlo method for evaluating uncertainty and expanded uncertainty. Metrologia 2006, 43, S178–S188. [CrossRef] © 2017 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).

Journal

BuildingsMultidisciplinary Digital Publishing Institute

Published: Mar 6, 2017